beautypg.com

VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 53

background image

-

Min./max.-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and

'Cal_type' = 1 (Online) the 'Cal_point_hi' is automatically set to the current sensor value.

The unit is defined in 'Level_unit'

l

CAL_LEVEL_LO

-

Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and

'Cal_type' = 1 (Online), the 'Cal_point_lo' is automatically set to the current sensor

value. The unit is defined in 'Level_unit'

l

CAL_TYPE

-

Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value.

Online: current sensor value determines 'Cal_point_hi/lo'

l

level

-

Value after min./max.-adjustment

l

level_unit

-

Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'

l

level_offset

-

Offset that is added to the 'Level' value. Unit derives from 'Level_unit'

l

SENSOR_OFFSET

-

Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'

l

end_of_operation_range

-

Set up to suit the process conditions

l

begin_of_operation_range

-

Set up to suit the process conditions

l

product_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

liquids_medium_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

solids_medium_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

liquids_vessel_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

solids_vessel_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

fast_level_change

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

Supplement

VEGASON 66 - Foundation Fieldbus

53

28795

-EN

-060731