4 mounting, 1 general instructions – VEGA VEGASON 66 Foundation Fieldbus User Manual
Page 11
4 Mounting
4.1 General instructions
Make sure that the wetted parts of VEGASON 66, especially
the seal and process fitting, are suitable for the existing
process conditions such as pressure, temperature etc. as well
as the chemical properties of the medium.
You will find specification in chapter "Technical data" in the
"Supplement".
Select an installation position you can easily reach for
mounting and connecting as well as later retrofitting of an
indicating and adjustment module. The housing can be rotated
by 330° without the use of any tools. You can also install the
indicating and adjustment module in four different positions
(each displaced by 90°).
Use the recommended cables (see chapter "Connecting to
power supply") and tighten the cable gland.
You can give your VEGASON 66 additional protection against
moisture penetration by leading the connection cable down-
ward in front of the cable entry. Rain and condensation water
can thus drain off. This applies mainly to mounting outdoors, in
areas where moisture is expected (e.g. by cleaning processes)
or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Materials, wetted parts
Installation location
Moisture
VEGASON 66 - Foundation Fieldbus
11
Mounting