beautypg.com

4 setup procedure – VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 32

background image

6.4 Setup procedure

As VEGASON 66 is a distance measuring instrument, the

distance from the sensor to the product surface is measured.

To have the real product level displayed, an allocation of the

measured distance to the percentage height must be made. To

carry out this adjustment, the distance is entered with full and

empty vessel. If these values are not known, an adjustment

with the distance values, e.g. 10 % and 90 % is also possible.

Starting point for these distance specifications is always the

the lower side of the flange (flange version, for all other

versions the lower side of the transducer.
The actual level is then calculated on the basis of these

entered values. At the same time, the operating range of the

sensor is limited from maximum range to the requested range.
The real product level during this adjustment is not important,

because the min./max. adjustment is always carried out

without changing the product level. These settings can be

made ahead of time without the instrument having to be

installed.
In the main menu item "Basic adjustment", the individual

submenu items should be selected one after the other and

provided with the correct parameter values.
Start your parameter adjustment with the following menu items

of the basic adjustment:
Proceed as follows:
1 Move from the measured value display to the main menu

by pushing [OK].

Basic adjustment

Display

Diagnostics

Service

Info

2 Select the menu item "Basic adjustment" with [->] and

confirm with [OK]. Now the menu item "Min. adjustment" is

displayed.

Min. adjustment

0.00 %

=

5.000 m(d)

4.000 m(d)

Parameter adjustment

Carry out min. adjustment

Setup with the indicating and adjustment module PLICSCOM

32

VEGASON 66 - Foundation Fieldbus

28795

-EN

-060731