6 Plug the connection head to the transducer tube. Do not

squeeze any cables. The cylinder is in the correct position,

if the lower notch (2) of the transducer tube is no longer

visible

7 Tighten the screws (5) on the cylinder moderately with a

hexagon spanner (size 4)

8 Loosen terminal screw of the swivelling holder (3) with a

fork spanner (SW 13)

9 Direct the sensor with the swivelling holder to the

measured product

10 Fasten the swivelling holder with screw (3), torque max.

20 Nm

11 Secure screw (3) with lacquer or similar to ensure

permanent tightness of the swivelling holder

12 Rotate the connection head in such a way that the cable

entry points downwards (moisture can drain off). Fasten

the cylinder with screws (5); torque max. 5 Nm

13 Insert the plug at the end of the transducer cable into the

socket on the remote electronics