3 exchange the electronics module – VEGA VEGASON 66 Foundation Fieldbus User Manual
Page 41
?
Instrument does not appear during connection setup
l
Incorrect termination
à
Check termination at the beginning and end points of
the bus and terminate, if necessary, according to the
specification
l
Instrument not connected to the segment
à
Check and correct
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
?
E013
l
no measured value available
à
sensor in boot phase
à
sensor does not find an echo, e.g. because of faulty
installation or incorrect parameter adjustment
?
E017
l
Adjustment span too small
à
Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E036
l
no operable sensor software
à
Carry out software update or send instrument for repair
?
E041
l
Hardware error, electronics defective
à
Exchange instrument or return instrument for repair
?
E113
l
Communication conflict
à
Exchange instrument or return instrument for repair
8.3 Exchange the electronics module
If the electronics module is defective, it can be replaced by the
user.
Fault messages via the indi-
cating/adjustment module
Maintenance and fault rectification
VEGASON 66 - Foundation Fieldbus