Instrument does not appear during connection setup

l

Incorrect termination

à

Check termination at the beginning and end points of

the bus and terminate, if necessary, according to the

specification

l

Instrument not connected to the segment

à

Check and correct

In Ex applications, the regulations for the wiring of intrinsically

safe circuits must be observed.

?

E013

l

no measured value available

à

sensor in boot phase

à

sensor does not find an echo, e.g. because of faulty

installation or incorrect parameter adjustment

?

E017

l

Adjustment span too small

à

Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E036

l

no operable sensor software

à

Carry out software update or send instrument for repair

?

E041

l

Hardware error, electronics defective

à

Exchange instrument or return instrument for repair

?

E113

l

Communication conflict

à

Exchange instrument or return instrument for repair

8.3 Exchange the electronics module

If the electronics module is defective, it can be replaced by the

user.

Fault messages via the indi-

cating/adjustment module

Maintenance and fault rectification

VEGASON 66 - Foundation Fieldbus

41