VEGA VEGASON 66 Foundation Fieldbus User Manual
Page 33
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the appropriate distance value in m (corresponding
to the percentage value) for the empty vessel (e.g. distance
from the sensor to the vessel bottom).
5 Save the settings with [OK] and move to "Max. adjustment"
with [->].
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
2 Enter the appropriate distance value in m (corresponding
to the percentage value) for the full vessel. Keep in mind
that the max. level must lie below the dead band.
3 Save the settings with [OK] and move to "Medium
selection" with [->].
Each product has different reflective properties. In addition,
there are various interfering factors which have to be taken into
account: agitated product surfaces and foam generation (with
liquids); dust generation, material cones and echoes from the
vessel wall (with solids). To adapt the sensor to these different
conditions, you should first select in this menu item "Liquid" or
"Solid".
Medium
Liquid
With solids, you can also choose between "Powder/Dust",
"Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted
perfectly to the product and measurement reliability, partic-
ularly in products with bad reflective properties, is considerably
increased.
Carry out max. adjustment
Medium selection
Setup with the indicating and adjustment module PLICSCOM
VEGASON 66 - Foundation Fieldbus
33
28795
-EN
-060731