3

2

1

Fig. 1: Example of a VEGABAR 61 with flange connection DN 50 PN 40 and
plastic housing
1

Housing cover with integrated indicating and adjustment module (optional)

2

Housing with electronics

3

Process fitting with measuring cell

3.2 Principle of operation

T

he VEGABAR 61 is a pressure transmitter with isolating diaphragm

for pressure measurement of highly corrosive and hot liquids.

T

he sensor element for measuring ranges up to 60 bar is the

CERTEC

®

measuring cell with rugged ceramic diaphragm. The

hydrostatic pressure of the product or the process pressure causes a
capacitance change in the measuring cell via the metal process
diaphragm and the isolating system.

1)

T

he sensor element for measuring ranges from 100 bar is a wire strain

gauge (DMS) on the rear of the process diaphragm. There, the
process pressure causes a resistance change, which is converted into
an appropriate output signal.

T

wo-wire electronics 4 … 20 mA/HART for power supply and

measured value transmission over the same cable.

T

he supply voltage range can differ depending on the instrument

version.

T

he data for power supply are specified in chapter "Technical data".

1)

T

he isolating system protects the sensor against corrosive products and

high temperatures. By selecting suitable diaphragm materials and isolating
liquids, systems with a temperature resistance up to 400 °C (752 °F) can be
achieved.

Application area

Functional principle

Power supply

VEGABAR

61 • 4 … 20

mA/HART

9

3 P

roduct description

27519

-