5

C

onfirm with [+] and move to max. adjustment with [->].

T

he min. adjustment is finished.

Information:
F

or an adjustment with filling, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

P

roceed as follows:

1

E

dit the % value in the menu item "Max. adjustment" with [OK].

M

ax. adjustment

+100

.0 %

=

+1000

.0 mbar

0000.0

mbar

Information:
T

he displayed pressure for 100 % corresponds to the nominal

measuring range of the sensor (in the above example 1 bar =
1000

mbar).

2

S

et the requested percentage value with [->] and [OK].

3

E

dit the requested mbar value with [OK].

4

S

et the requested mbar value with [+] and [->].

5

C

onfirm with [OK] and move to the menu overview with [ESC].

T

he max. adjustment is finished.

Information:
F

or an adjustment with filling, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Process pressure measurement

S

et up VEGABAR 61 in the following sequence:

1

S

elect application "Process pressure measurement"

2

S

elect the unit of measurement

3

C

arry out position correction

4

C

arrying out zero adjustment

5

C

arrying out span adjustment

I

n the menu item "Adjustment unit" you select the physical unit in which

the adjustment should be carried out, e.g. mbar, bar, psi…

Carrying out max. ad-
justment

Parameter ad-
justment "Proc-
ess pressure
measurement"

VEGABAR

61 • 4 … 20

mA/HART

37

6 S

et up with the indicating and adjustment module PLICSCOM

27519

-

EN