roceed as follows:
1
E
dit the mbar value in the menu item "zero" with [OK].
Z
ero adjustment
000.0 %
P
=
+0000
.0 mbar
0000.0
mbar
2
S
et the requested mbar value with [+] and [->].
3
C
onfirm with [+] and move to span adjustment with [->].
T
he zero adjustment is finished.
Information:
T
he zero adjustment shifts the value of the span adjustment. The span,
i.e. the difference between these values, however, remains un-
changed.
Information:
F
or an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"O
utside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]
.
P
roceed as follows:
1
E
dit the mbar value in the menu item "span" with [OK].
S
pan adjustment
100.0 %
P
=
+1000
.0 mbar
0000.0
mbar
Information:
T
he displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000
mbar).
2
S
et the requested mbar value with [->] and [OK].
3
C
onfirm with [OK] and move to the menu overview with [ESC].
T
he span adjustment is finished.
Information:
F
or an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"O
utside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]
.
Carrying out zero ad-
justment
Carrying out span ad-
justment
40
VEGABAR
61 • 4 … 20
mA/HART
6 S
et up with the indicating and adjustment module PLICSCOM
27519
-EN
-081209