Basic adjustment
I

f the "Reset" (sensor-specific basic adjustment) is carried out, the

sensor resets the values of the following menu items to the reset
values (see chart):

Menu section

Function

Reset value

B

asic settings

U

nit of measurement

bar

T

emperature unit

°C

Z

ero/Min. adjustment

M

easuring range begin

S

pan/Max. adjustment

M

easuring range end

D

ensity

1

kg/l

D

ensity unit

kg/l

D

amping

1

s

L

inearisation

linear

S

ensor-TAG

S

ensor

D

isplay

D

isplayed value 1

bar

D

isplayed value 2

%

D

isplay unit

V

olume/l

S

caling

0.00

to 100.0

D

ecimal point indication

8888.8

S

ervice

C

urrent output - characteristics

4 … 20

mA

C

urrent output - failure

<

3.6

mA

C

urrent output - min. current

3.8

mA

C

urrent output - max. current

20.5

mA

T

he values of the following menu items are not reset with "Reset:

Menu section

Function

Reset value

B

asic settings

P

osition correction

no reset

D

isplay

L

ighting

no reset

S

ervice

SIL

no reset

L

anguage

no reset

HART

mode

no reset

A

pplication

no reset

Reset

42

VEGABAR

61 • 4 … 20

mA/HART

6 S

et up with the indicating and adjustment module PLICSCOM