beautypg.com

4 mounting steps external housing – VEGA VEGABAR 61 4 … 20 mA_HART User Manual

Page 15

background image

4.3 Mounting steps, tube isolating diaphragm

according to DIN 11851

T

he isolating systems are temperature and pressure-aged at 80 °C

and 18 bar. The zero point is adjusted at 22 °C ±2 °C and a torque of
275 N

m. The defined installation position is: Tube isolating diaphragm

horizontally, VEGABAR 61 vertically.

F

or mounting, proceed as follows:

1

P

osition VEGABAR 61 with tube isolating diaphragm

2

T

ighten the threaded fittings step-by-step once on the right and on

the left

3

H

old VEGABAR 61, to avoid distortion from the defined installation

position.

Caution:
A

part from mounting, the tube isolating diaphragm must not be

permanently under torsion.

4

C

heck current after mounting. The current must be between 3.9

and 4.1 mA. In case of a deviating value, losen threaded fitting and
mount again.

Information:
B

y slightly increasing or reducing the torque, the current can be set

exactly to 20 mA.

4.4 Mounting steps external housing

1

M

ark the holes according to the following drilling template

2

D

epending on the mounting surface, fasten the wall mounting

plate with 4 screws

Wall mounting

VEGABAR

61 • 4 … 20

mA/HART

15

4 M

ounting

27519

-

EN

-081209