beautypg.com

VEGA VEGAMET 513 User Manual

Page 8

background image

8

VEGAMET 513

Product description

Electrical protective measures

Protection
- not mounted

IP 00

- mounted in

carrier BGT 596
- front side completely equipped

IP 40

- upper and lower side

IP 20

- wiring side

IP 00

- mounted in

housing type 505 or type 506
- terminal side

IP 20

- housing in general

IP 30

Protection class

II (in housing type 505)

Overvoltage category

II

Electrical separating measures

between
- power supply and all

other potentials

reliable separation acc. to VDE 0106, part 1

- reference voltage

250 V

- isolation resistance

2.5 kV/AC

Between
- meas. data input and all

other potentials

reliable separation acc. to VDE 0106, part 1

- reference voltage

250 V

- isolation resistance

2.5 kV/AC

Between
- DISBUS and all other potentials

potential separation
- reference voltage

50 V

- isolation resistance

0.5 kV/AC

Mechanical data

Series

module unit for carrier BGT 596
or housing type 505

Dimensions

B = 25.4 mm (5 TE), H = 128.4 mm, T = 162 mm

CE conformity

The VEGAMET signal conditioning instrument meets the protective regulations of EMC
(89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following
standards:
EMC

Susceptibility

EN 50 081 - 2: 1993

Immission

EN 50 082 - 2: 1995

NSR

EN 61 010 - 1: 1993