2 mounting, Mounting in carrier, Mounting in single housing – VEGA VEGAMET 513 User Manual
Page 10: Transparent cover, Coding
10
VEGAMET 513
2 Mounting
VEGAMET 513 signal conditioning
instruments can be either mounted with a
module in a carrier BGT 596 or BGT
596 Ex.M or in a single housing type 505.
Mounting in carrier
Mount the respective module (standard or Ex
version) in your carrier. Wire the terminals of
the multipoint connector according to the
wiring plan.
Module
Multipoint connector DIN 41 612, series F, 33-
pole (d, b, z) with coded pins and mounting
material for mounting in carrier BGT 596 or
BGT 596 Ex.M.
Module Ex
Multipoint connector DIN 41 612, series F, 33-
pole (d, b, z) with coded pins, Ex separating
chamber and mounting material for mounting
in carrier BGT 596 Ex.M.
The multipoint connector is available in the
following versions:
- Wire-Wrap standard connection
1.0 x 1.0 mm
- Plug connection 2.8 x 0.8 mm
- Termi-Point standard connection
1.6 x 0.8 mm
- Soldering connection
- Screw terminals 0.5 mm
2
For further mounting information, see the
operating instructions of the carrier.
Mounting in single housing
Either screw the housing socket directly to
the mounting plate or plug it onto a carrier rail
(35 x 15 acc. to EN 50 022 or 32 acc. to
EN 50 035). Connect the terminals according
to the wiring plans on the following pages.
For further mounting information see the oper-
ating instructions of the housing.
Transparent cover
To protect the instrument against unauthor-
ised adjustment, the front plate of VEGAMET
can be provided with a lockable transparent
cover.
Coding
To prevent an interchanging of the different
signal conditioning instruments, the multipoint
connector of carrier or the housing can be
provided with coded pins.
Note:
The coding is absolutely necessary for Ex
instruments!
The multiple plug of the signal conditioning
instrument is equipped with respective holes
(mechanical coding). Instrument coding
ensures that the different signal conditioning
instruments cannot be interchanged. The
appropriate coded pins are supplied with
each module or housing. Equip the multipoint
connector with these coded pins acc. to the
following table.
Instrument
Ex
coding
coding
VEGAMET 513
a1 / c5
–
VEGAMET 513 Ex
a1 / c5
c23
Mounting
o 9 o
z b d
o 1 o
a c
a5
o 3 o
o 5 o
o 7 o
o11o
o13o
o15o
c5
o17o
o19o
o21o
o23o
o25o
o27o
o29o
o31o
c23