VEGA VEGAMET 513 User Manual
Page 7
VEGAMET 513
7
Product description
Relay output
Number
1 fail-safe relay
Contact
floating spdt
Contact material
AgNi, hard gold plated
Turn-on voltage
min. 10 mV DC
max. 250 V AC/DC
Switching current
min. 10 µA
max. 3 A AC, 1 A DC
Breaking capacitance
max. 500 VA, 54 W
DISBUS output
Function
for linking the signal conditioning instruments
and for connection of digital indicating
instruments
Connection cable
2-wire standard cable (screening is
recommended)
max. cable length
1000 m
Indicating elements
Clear text indication
LC display
4- line, 6 digits each
background lighting
Analogue indication
LED chain consisting of:
11 segments 0 % … 100 %
shows the actual value of the measurement
loop
LEDs in front plate
green: operating voltage on
red: fault signal (LED lights with deenergised
relay)
Adjustment elements
Front plate
6 keys for configuration and parameter
adjustment
Circuit board
rotary switch for adjustment of the instrument
address on DISBUS
Ambient conditions
Permissible ambient temperature
-20°C … +60°C
Storage and transport temperature
-40°C … +80°C
Electrical connection
Multiple plug component
acc. to DIN 41 612, series F, 33-pole, 3 lines
d, b, z (partly equipped)
Carrier BGT 596 (Ex)
connection to the appropriate module
Housing type 505
connection to screw terminals (max. 2.5 mm
2
)