Settings in the "reduced menu"
6.5 Integration time
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Adjust
ment
Signal-
condit
ioning
Sca-
ling
Integr
ation
time s
0
Meas. value
indication
If the integration time is set to 0 s (factory
setting), each quick change of the product
surface (e.g. waves) will be immediately
detected and interpreted as level change. All
output values of VEGAMET will react
immediately to the wave movements. To
avoid this, the integration time can be
increased (max. 600 s are possible with
VEGAMET). The higher the time adjustment,
the slower the measurement reacts.
6.6 Outputs
Meas. value
indication
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Adjust
ment
Signal-
condit
ioning
Out-
puts
Current
out-
put 1
4/20mA
Volt
out-
put 1
0/10V
0/20mA
20/4mA
20/0mA
10/2V
10/0V
2/10V
The current output of VEGAMET is adjusted
to 4 … 20 mA. By pushing [+] or [–] and
[OK] the outputs can be adjusted to the
following values: 0/20 mA, 20/4 mA and
20/0 mA.
For voltage output, the following options are
available apart from the preadjustment
(0/10 V): 10/2 V, 10/0 V and 2/10 V.
6.7 Simulation
To check outputs and connected instru-
ments, you can adjust any individual
percentage value with the keys [+] and [–] in
this menu item. Initial point is always the
actual measured value. The indicated value
flashes when simulation is activated. 15
minutes after setting the simulated value, the
simulation automatically terminates and
resets to meas. value indication.