Adjustment

4 Adjustment

4.1 Indicating and adjustment ele-

ments

Circuit board

A rotary switch is located on the circuit
board. It is used for adjustment of the instru-
ment address on DISBUS. This setting is
necessary if several VEGAMET signal condi-
tioning instruments are linked via the
DISBUS.

The adjustment range 1 … F corresponds to
the DISBUS addresses 1 … 15.
Factory setting: 1

Note:

With address 0 the VEGAMET does not par-
ticipate in the DISBUS communication.

Rotary switch

The set DISBUS address can be displayed
via the LC display without removing the in-
strument.

Note

If several VEGAMET are linked via the
DISBUS, each address must only be
assigned once!

1 LCD (4 lines with 6 figures each, illuminated) for clear text

indication

2 LED chain (yellow) for quasi-analogue indication of the

measured value

3 Keys for menu adjustment
4 Connection socket for VEGACONNECT
5 LED (red), lights if fail safe relay is deenergised
6 LED (green), lights if operating voltage is on