Diagnostics

9.5 Error codes

Error code

Meaning

E004

This operation is not supported by the instrument (different software versions).
You have tried to activate a function with a newer software version of VEGA
Visual Operating in an instrument with older software version. However, the
instrument cannot support this operation.
Have the software of your instrument updated.

E014

Possible short-circuit
Probable reasons:
- short-circuit
- sensor is defective
Check the connection cable and, if necessary, the sensor.
Probably
- an incorrect measuring range has been set on the capacitive electrode.
Adjust a smaller range.

E015

Possible line break
Probable reasons:
- no sensor connected
- line break
- sensor is defective
Check the connection cable and, if necessary, the sensor.

E016

Empty/full adjustment reversed. The values for the empty adjustment are
above the values for the full adjustment. Carry out the adjustment again.

E017

Adjustment span too small. The adjustment values are too close together or are
identical. Carry out the adjustment again.
Probably
- an incorrect measuring range has been set on the capacitive electrode.
Adjust a higher range.

E021

Span of the scaling values too small or values reversed. The scaling values are
too close together or are identical. Please check the scaling.

E022

Scaling span too big.

E027

Actual measured value is less than -10 %.

E028

Actual measured value is more than 110 %.

E031

Same DISBUS address. At least one other instrument with the same DISBUS
address is connected to the DISBUS. Please check the DISBUS address.