7.4 Adjustment

The

adjustment with medium

corresponds

to the procedure in the reduced menu (see
appropriate chapter).

- if the medium is changed later on (medium

with another density value or DK value)
and no new adjustment can be made
or

- if the MET indication and the DIS outputs

relate to height in meters,

Please note the following:
In applications with hydrostatic pressure
transmitters, the adjusted density value (see
menu Parameter - Conditioning - Scaling -
Density) must correspond to the value of the
medium. In applications with capacitive elec-
trodes, the adjusted DK value must corre-
spond to the value of the medium.

Settings in the "extended menu"

Param.
TAG-
No. 1

Adjust-
ment

with
medium

without
medium

Min-
adjust
at %

0,0

Max-
adjust
at %

100,0

Adjust-
ment

mA

Offset
cor-
rection

0%
at

mA

0,000

100%
at

mA

1,000

Sensor
unpres-
sur'd ?
OK ?

Offset
corr.
Now!
OK ?

TAG -
No. 1
%
xx,x

For the

adjustment without medium,

two

anticipated values for level, gauge, etc.
corresponding to 0 % and 100 % must be
entered.

The menu item "Offset correction" is opened
when hydrostatic pressure transmitters are
connected. The offset correction should be
carried out after installation of the sensor as
the sensor values can differ slightly due to
different installation positions (vertical or
horizontal installations). With the offset cor-
rection, the meas. data of the unpressurised
sensor (vessel empty) are detected as cor-
rection values and taken into account in all
subsequent measurements.