User interface, Front panel, User lines – Xantrex Technology XDI2048 User Manual
Page 48: User interface –6, Front panel –6 user lines –6, Table 3-1, Front panel led functions –6, Table 3-2, User line pins –6, Front panel user lines
![background image](/manuals/230478/48/background.png)
Inverter Module Installation and Operation
3-6
TM-DIOP-01XN-01
User Interface
Front Panel
User Lines
The port with user lines is located at the rear panel of the rack mount
frame (Figure 2-3). See Figure 2-7. The following table lists the signals:
Table 3-1 Front Panel LED Functions
Red LED
Green LED
Function
ON
OFF
A continuously incompatible operating condition
exists and an alarm has tripped. See “Protections
and Alarms” on page 3–7). The inverter is
automatically turned off until the fault/alarm has
been cleared.
OFF
ON
Regular operating conditions. Output is on and
delivering power.
OFF
fast flashing
Self-Diagnostic mode. Prior to enabling the
inverter the unit always performs a self-check and
diagnostics.
OFF
slow-short flash Stand-by mode.
Table 3-2 User Line Pins
Pin Name
Function
1
User_Ground
All user lines are referenced to user_gnd. User_gnd is
isolated from both the input DC power and the output AC
power.
2
Shut_Down
This is an input pin. The input impedance is 100
Ω in
parallel with 20 pF. A logic high (1.25 V to 5 V) would set
the inverter into Standby Mode (see page 3–5). If pin 2 is
floating, the internal pull_down resistor of 100
Ω will
force a logic “0” and this pin becomes inactive.
3
Fault_Flag
This is an output pin. A logic high (5 V) indicates that an
alarm has tripped. The output of the inverter is, therefore,
disabled.
4
Auxiliary_Line This is an output pin. The functionality of this user line is
factory preset. It can be user configured if the Ethernet
option is installed.
5
Inverter_On
This is an output pin. A logic high (5 V) indicates that the
inverter is in an “on” state and delivering AC power to the
AC output power terminal.