York YHJD18 User Manual
Page 32
397855-YTG-G-0509
32
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
Continued on next page.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJD
42S41S1
EVAPORATOR COIL MODEL NO
FC/MC/PC/UC48
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1200
1400
1600
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
48.7 3.5 4.1 48.7 3.5 4.1 48.7 3.4 4.2
70
47.8 3.8 3.6 48.6 3.8 3.7 49.5 3.8 3.8
80
46.8 4.2 3.3 48.6 4.2 3.4 50.3 4.1 3.6
47
60
42.5 3.3 3.8 42.9 3.3 3.8 43.3 3.2 3.9
70
42.3 3.6 3.4 42.7 3.6 3.5 43.1 3.6 3.6
80
42.0 3.9 3.1 42.4 3.9 3.2 42.9 3.9 3.3
40
60
40.1 3.2 3.7 40.5 3.2 3.7 40.8 3.2 3.8
70
39.1 3.5 3.3 39.6 3.5 3.3 40.0 3.5 3.4
80
38.2 3.8 2.9 38.7 3.8 3.0 39.2 3.8 3.0
30
60
33.5 3.8 2.6 33.8 3.7 2.7 34.1 3.7 2.7
70
34.8 3.4 3.0 34.5 3.4 3.0 34.1 3.4 2.9
80
36.2 3.1 3.4 35.1 3.1 3.3 34.1 3.1 3.2
17
60
27.8 3.6 2.2 28.4 3.6 2.3 29.1 3.6 2.4
70
28.3 3.3 2.5 28.8 3.3 2.5 29.2 3.3 2.6
80
28.8 3.0 2.8 29.1 3.0 2.8 29.4 3.0 2.8
10
60
26.3 3.6 2.1 26.9 3.6 2.2 27.6 3.6 2.2
70
25.6 3.3 2.3 26.8 3.3 2.4 28.0 3.3 2.5
80
24.8 3.0 2.4 26.6 3.0 2.6 28.4 3.0 2.8
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
MBH
KW
COP
–
FC/MC/PC60
1.00 1.06 0.94
–
HC42
0.99 0.99 1.00
–
HC60
1.00 1.06 0.94
–
HD60 0.99
0.89
1.11
AHP/SHP48
–
1.00
1.00
1.00
AHX42
–
0.98
1.05
0.93
AHX48
–
0.98
1.07
0.92
AV/SV*48
–
0.98
1.05
0.94
F4FP045
–
1.01 1.07 0.94
F5FP048
–
0.99 1.01 0.98
F6FP042
–
0.99
1.06
0.94
F6FP048
–
0.99
1.09
0.91
MA14D
FC/MC/PC48D
1.00 1.00 1.00
MA16C
FC/MC/PC48C
1.00 1.00 1.00
MV16C
FC/MC/PC48C
0.99 0.99 1.00
MV20D
FC/MC/PC48D
0.98 0.98 1.00
MA14D
FC/MC/PC60D
1.00 1.06 0.94
MA16C
FC/MC/PC60C
1.00 1.06 0.94
MV20D
FC/MC/PC60D
0.98 1.04 0.94