beautypg.com

York YHJD18 User Manual

Page 3

background image

Johnson Controls Unitary Products

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting

line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator +

adder for line set.

System Charge for Various Matched Systems

Outdoor Unit

YHJD

18S41S1

YHJD

24S41S1

YHJD

30S41S1

YHJD

36S41S1

YHJD

42S41S1

YHJD

48S41S1

YHJD

60S41S2

Required Orifice or TXV

1

1TVM04E1

1TVM04G1

1TVM04G1

1TVM04H1

1TVM04H1

1TVM04J1

1TVM04K1

Factory Charge, lbs-oz

6 - 5

8 - 7

9 - 12

9 - 15

9 - 12

13 - 9

13 - 6

Indoor Coil

2,3

Additional Charge, Oz

FC/MC/PC/UC18AB

0

FC/MC/PC/UC24AB

4

FC/MC/PC30AB

4

FC/MC/PC32A

0

FC/MC/PC35BC

0

FC/MC/PC37A

6

0

0

FC/MC/PC43BC

6

0

0

FC/MC/PC/UC48CD –

10

0

FC/MC/PC/UC60CD

0

0

FC/MC62D

12

0

HC18A

1

HC30A

10

0

HC36B

0

HC42

0

0

HC60

0

0

HD24

14

HD36

2

HD48

8

8

HD60

0

7

AHP18

0

AHP30

0

AHP36

0

0

AHP/SHP48

0

0

AHP/SHP60

0

AHX30

0

AHX36

6

0

0

AHX42

0

AHX48

0

0

AHX60

0

AV*24

3

AV*36

6

0

0

AV/SV*48

0

0

AV/SV*60

0

F4FP24

0

F4FP45

0

0

F5FP48

0

0

F4FV60

0

F5FP60

0

F6FP030

+ 0

F6FP036

+ 0

+ 0

F6FP042

+ 10

+ 0

F6FP048

+ 0

+ 0

F6FP060

0

FOOTNOTES:

1. For applications requiring a TXV use 1TVM0 series kit.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.