York YHJD18 User Manual
Page 22
397855-YTG-G-0509
22
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO.
YHJD
30S41S1
INDOOR COIL MODEL NO.
AHP36
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
28.5 30.9 31.1 34.0 37.0 30.8 32.4 32.4 35.6 38.7 33.1 33.9 33.7 37.2 40.5
S.C.
28.5 26.1 22.3 22.1 18.6 30.8 29.7 24.5 24.4 19.8 33.1 33.4 26.8 26.7 21.1
KW
1.7 1.8 1.8 1.8 1.7 1.7 1.8 1.8 1.7 1.7 1.7 1.8 1.8 1.7 1.7
75
T.C.
27.1 29.1 29.1 32.0 35.3 29.2 30.3 30.3 33.4 36.6 31.3 31.5 31.5 34.7 37.9
S.C.
27.1 25.2 21.4 21.3 17.7 29.2 28.2 23.6 23.5 18.9 31.3 31.3 25.8 25.7 20.1
KW
1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
85
T.C.
25.7 27.2 27.2 30.0 33.6 27.6 28.2 28.2 31.2 34.5 29.5 29.2 29.2 32.3 35.4
S.C.
25.7 24.3 20.5 20.4 16.8 27.6 26.7 22.7 22.6 17.9 29.5 29.2 24.8 24.7 19.1
KW
2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
95
T.C.
24.3 25.3 25.3 28.1 31.8 26.0 26.1 26.1 29.0 32.3 27.7 26.8 27.0 29.9 32.9
S.C.
24.3 23.4 19.6 19.6 15.9 26.0 25.2 21.7 21.7 17.0 27.7 26.8 23.9 23.7 18.0
KW
2.2 2.2 2.2 2.3 2.3 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.3
105
T.C.
22.6 23.3 23.0 25.7 29.1 24.1 24.2 23.7 26.4 29.6 25.6 25.1 24.4 27.2 30.1
S.C.
22.6 22.1 18.6 18.6 14.9 24.1 23.7 20.5 20.7 16.0 25.6 25.1 22.4 22.7 17.1
KW
2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.5 2.5
115
T.C.
21.0 21.3 20.9 23.4 26.4 22.3 22.3 21.3 24.0 26.9 23.6 23.4 21.8 24.5 27.4
S.C.
21.0 20.8 17.7 17.7 13.9 22.3 22.2 19.3 19.7 15.0 23.6 23.4 20.9 21.8 16.1
KW
2.5 2.5 2.5 2.6 2.7 2.6 2.6 2.5 2.6 2.7 2.6 2.6 2.6 2.6 2.7
125
T.C.
19.4 19.3 18.7 21.1 23.7 20.5 20.5 19.0 21.5 24.2 21.6 21.6 19.3 21.9 24.7
S.C.
19.4 19.3 16.7 16.8 12.9 20.5 20.5 18.1 18.8 14.1 21.6 21.6 19.3 20.8 15.2
KW
2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.7 2.8 2.9 2.8 2.8 2.7 2.8 2.9
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC32
0.99 0.99 1.00
–
FC/MC/PC35
0.99 0.99 1.00
–
FC/MC/PC37
1.01 1.01 1.00
–
FC/MC/PC43
1.01 1.01 1.00
–
HC36
0.99 0.99 1.00
–
HC42
1.01 1.01 1.00
–
HD48
1.01 1.01 1.00
AHP36
–
1.00 1.00 1.00
AHX36
–
1.03
1.06
0.91
AV36
–
1.04 1.05 1.00
F4FP040
–
0.99 0.97 1.00
F6FP036
–
1.01
1.01
0.93
MA12B
FC/MC/PC35B
0.99 0.99 1.00
MV12B
FC/MC/PC35B
1.01 1.01 1.00
MV16C
FC/MC/PC35C
1.01 1.01 1.00
MA12B
FC/MC/PC43B
1.01 1.01 1.00
MV12B
FC/MC/PC43B
1.03 1.03 1.00
MV16C
FC/MC/PC43C
1.03 1.03 1.00
Furnaces
Coils
T.C.
S.C
KW
T*(8,L)X*A12
FC/MC/PC37A
1.05
1.10
0.95
T*9X*B12
FC/MC/PC43B
1.05
1.10
0.94
T*(8,L)X*B12
FC/MC/PC43B
1.05
1.10
0.95
Y
*(8,L)C*A12
FC/MC/PC37A
1.01 1.01 0.97
Y
*(8,L)C*B12
FC/MC/PC43B
1.02 1.02 0.94
(
Y
*9C/T*9V)*B12 FC/MC/PC43B
1.01 1.02 0.96
Y
*(8,L)C*C16
FC/MC/PC43C
1.03 1.03 0.93
Y
*(8,L)C*C20
FC/MC/PC43C
1.02 1.04 0.92
(
Y
*9C/T*9V)*C16 FC/MC/PC43C
1.02 1.02 0.95
(
Y
*9C/T*9V)*C20 FC/MC/PC43C
1.02 1.03 0.93
Y
*(8,L)C*C16
HC42
1.02 1.03 0.93
Y
*(8,L)C*C20
HC42
1.02 1.03 0.92
(
Y
*9C/T*9V)*C16 HC42
1.02 1.02 0.95
(
Y
*9C/T*9V)*C20 HC42
1.02 1.03 0.93
Y
*(8,L)C*A12
HD36
0.99 0.97 0.95
Y
*(8,L)C*B12
HD36
0.99 0.97 0.93
Y
*(8,L)C*C16
HD36
0.99 0.97 0.93
Y
*(8,L)C*C20
HD36
1.00 1.00 0.93
(
Y
*9C/T*9V)*B12 HD36
0.99 0.97 0.94
(
Y
*9C/T*9V)*C16 HD36
0.99 0.97 0.93
(
Y
*9C/T*9V)*C20 HD36
0.99 0.97 0.93