COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO.
YHJD
18S41S1
INDOOR COIL MODEL NO.
AHP18
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
450
600
750
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
17.6 20.2 20.2 22.5 24.9 20.4 21.5 21.8 24.2 26.7 23.2 22.7 23.4 25.9 28.4
S.C.
16.0 14.5 12.5 12.6 10.7 18.5 17.5 14.7 14.7 11.9 21.1 20.6 16.9 16.9 13.2
KW
1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0
75
T.C.
16.6 18.6 18.6 20.7 23.0 19.1 19.9 19.9 22.1 24.6 21.6 21.2 21.2 23.6 26.1
S.C.
15.0 13.8 11.8 11.9 10.0 17.3 16.5 14.0 14.0 11.2 19.6 19.3 16.1 16.1 12.4
KW
1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
85
T.C.
15.6 16.9 16.9 19.0 21.2 17.7 18.3 18.0 20.1 22.5 19.9 19.7 19.1 21.3 23.7
S.C.
14.1 13.1 11.1 11.2 9.3 16.1 15.5 13.2 13.2 10.5 18.1 17.9 15.3 15.3 11.6
KW
1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
95
T.C.
14.5 15.3 15.3 17.2 19.3 16.4 16.8 16.1 18.1 20.3 18.3 18.3 16.9 19.0 21.4
S.C.
13.2 12.4 10.4 10.5 8.6 14.9 14.5 12.4 12.5 9.7 16.6 16.6 14.5 14.5 10.8
KW
1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
105
T.C.
13.2 13.6 13.4 15.2 17.0 14.7 14.9 14.2 16.0 17.9 16.3 16.3 15.0 16.7 18.7
S.C.
11.9 11.3 9.6 9.7 7.8 13.3 13.0 11.3 11.5 8.9 14.8 14.8 13.1 13.3 10.1
KW
1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5
115
T.C.
11.8 12.0 11.5 13.2 14.8 13.1 13.1 12.3 13.9 15.5 14.3 14.3 13.2 14.5 16.1
S.C.
10.7 10.4 8.9 9.0 7.1 11.9 11.7 10.3 10.6 8.2 13.0 13.0 11.7 12.3 9.3
KW
1.5 1.5 1.5 1.5 1.6 1.5 1.6 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6
125
T.C.
10.5 10.3 9.7 11.2 12.6 11.4 11.3 10.5 11.8 13.1 12.3 12.3 11.3 12.3 13.6
S.C.
9.5 9.4 8.2 8.3 6.3 10.4
10.3 9.2 9.7 7.4 11.2
11.2
10.3
11.2 8.6
KW
1.6 1.6 1.6 1.6 1.7 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC18
0.99 0.99 1.00
–
FC/MC/PC24
1.01 1.01 1.00
–
HC18
0.99 0.99 1.00
–
HC30
1.01 1.01 1.00
–
HD24
1.03 1.02 1.00
AHP18
–
0.97 0.96 1.00
AV24
–
1.03 1.02 1.00
F4FP024
–
1.00 0.99 1.00
MA08B
FC/MC/PC18B
0.99 0.99 1.00
MV12B
FC/MC/PC18B
1.02 1.01 1.00
MA08B
FC/MC/PC24B
1.01 1.01 1.00
MV12B
FC/MC/PC24B
1.04 1.04 1.00
Furnaces
Coils
T.C.
S.C.
KW
Y
*(8,L)C*A12
FC/MC/PC18A
1.03 1.05 0.93
Y
*(8,L)C*B12
FC/MC/PC18B
1.02 1.01 0.92
(
Y
*9C/T*9V)*B12 FC/MC/PC18B
1.03 1.04 0.92
Y
*(8,L)C*A12
FC/MC/PC24A
1.06 1.08 0.94
Y
*(8,L)C*B12
FC/MC/PC24B
1.04 1.04 0.92
(
Y
*9C/T*9V)*B12 FC/MC/PC24B
1.06 1.08 0.93
Y
*(8,L)C*A12
FC/MC/PC30A
1.06 1.08 0.94
Y
*(8,L)C*B12
FC/MC/PC30B
1.04 1.04 0.92
(
Y
*9C/T*9V)*B12 FC/MC/PC30B
1.06 1.08 0.93
Y
*(8,L)C*A12
HC18
1.03 1.05 0.93
Y
*(8,L)C*A12
HC30
1.04 1.04 0.94
Y
*(8,L)C*A12
HD24
1.06 1.08 0.94
Y
*(8,L)C*B12
HD24
1.05 1.04 0.92
(
Y
*9C/T*9V)*B12 HD24
1.06 1.08 0.93
Y
*(8,L)C*A12
UC18A
1.04 1.05 0.93
Y
*(8,L)C*B12
UC18B
1.03 1.03 0.92
(
Y
*9C/T*9V)*B12 UC18B
1.04 1.05 0.92
Y
*(8,L)C*A12
UC24A
1.06 1.09 0.94
Y
*(8,L)C*B12
UC24B
1.05 1.05 0.92
(
Y
*9C/T*9V)*B12 UC24B
1.06 1.09 0.93
Y
*(8,L)C*A12
UC30A
1.06 1.09 0.94
Y
*(8,L)C*B12
UC30B
1.05 1.05 0.92
(
Y
*9C/T*9V)*B12 UC30B
1.06 1.09 0.93
Furnaces
Coils
T.C.
S.C.
KW