Step 4: Wiring the Inverter
975-0239-01-01
2–23
AUX Port
The XW Series has a 12 Vdc auxiliary output that can be configured to trigger in response
to one of the following battery conditions:
•
low battery voltage
•
high battery voltage
•
low battery temperature
•
high battery temperature
•
any device fault
The auxiliary output can also be triggered manually.
The 12 Vdc output can be used to trigger a relay to disconnect batteries from the inverter/
charger when battery voltage or temperature are out of the ideal range.
The auxiliary output is designed to provide the following functions:
•
Auxiliary 12 Vdc power supply
•
Remote Power Off
AUX+12V Voltage Supply
DC voltage is available between JU-1 (AUX +12 V) and JU-3 (AUX-COM, signal return).
The power available at these terminals is 12 Vdc and maximum current is 0.25 Adc
(3 watts).
AUX+12 V and AUX-COM terminals can be used: to power a relay (3 watts maximum).
Additional fuses are not required, but may be required for some installations.
AUX +12 V voltage supply can be programmed for different tasks ON and OFF using the
XW System Control Panel.
Default status of AUX+12 V is OFF.