beautypg.com

Xantrex Technology XW POWER SYSTEM XW4024-120/240-60 User Manual

Page 20

background image

Introduction

1–4

975-0239-01-01

The XW Conduit Box comes in two pieces and mounts directly to the bottom of the
inverter/charger with keyhole slots and screws. It is secured to the inverter by two
#10-32 screws and is secured to the wall by two screws (not provided).
Internal wire barriers (or raceways) are included to keep communications wires separate
from AC and DC power wires. The XW Conduit Box also includes multiple cable strap
points.

XW Power Distribution Panel Panel and XW Conduit Box

The XW Power Distribution Panel (FGA: 865-1015) includes a mounting plate and XW
Conduit Box. It is factory wired and labelled with everything to support a code-compliant
single-inverter installation. It is designed to mount on the right side of the inverter/charger,
but it can also be configured to mount on the left side. Internal wiring and breakers can be
added to expand the XW Power System with up to three inverters, four charge controllers,
or other equipment to support 120/240-volt, 3-wire, single-phase systems.
The XW Power Distribution Panel and XW Conduit Box interface with:

XW4024, XW4548, and XW6048 inverter/chargers

XW Solar Charge Controllers (requires customer supplied breakers and wiring)

C-Series Charge Controllers (requires customer supplied breakers and wiring).

Internal wire barriers (or raceways) are included to keep communications wires separate
from AC and DC power wires.

Figure 1-4 Power Distribution Panel and XW Conduit Box

XW Power Distribution Panel

Mounting Plate

XW Conduit Box

XW Power Distribution Panel includes:

Power Distribution Panel enclosure with a field-reversible panel door

Mounting Plate

XW Conduit Box

The panel door can be mounted on the right or left side of the XW Power
Distribution Panel
.

AC Knockout slots = 8 (for dual 60A Square D, type QOU breakers)*
DC Knockout slots = 8 small (for 60A DC breakers) and 3 large (for GJ breakers)

*AC Breakers cannot exceed 60A.

The enclosure comes pre-wired with:

3x 60A, 120/240 Vac, 2-pole, Square-D, Type QOU, DIN-rail mounted
AC breakers (pre-wired to connect to one XW inverter)

1x GJ250A 160 Vdc, 3/8" stud DC breaker

1x Ground terminal bus bar

1x Neutral terminal bus bar

1 pair #4/0 AWG Battery Cables

XW PDP Dimensions:
30" (761mm) H x 16" (406mm) W x 8 ¼" (210mm) D
Depth from the wall = 8 ¾" (223 mm)

This manual is related to the following products: