beautypg.com

Xantrex Technology XW POWER SYSTEM XW4024-120/240-60 User Manual

Page 35

background image

Step 4: Wiring the Inverter

975-0239-01-01

2–11

Torque Values for the XW Power Distribution Panel

Inverter Grounding

Backfeed Protection Requirements

Table 2-7 Torque Values for AC Disconnects and AC Breakers

Wire Size

Torque Value

AWG

In-lb

N-m

16–10

45

5

8

45

5

6–4

45

5

Table 2-8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus, and DC
Positive Bus in the XW Power Distribution Panel

Wire Size

Torque Value

AWG

In-lbs

N-m

14 - 10

35

4.0

8

40

4.5

6 - 4

45

5.1

3 - 2/0

50

5.6

Table 2-9 Torque Values for the Power Distribution Bars in the XW Power Distribution
Panel

Wire Size

Torque Value

AWG

In-lbs

N-m

14 - 10

35

4.0

8

40

4.5

6 - 4

45

5.1

3 - 2/0

50

5.6

Table 2-10 Torque Values for the Battery Cables to the DC Negative Bus, and DC
Positive Bus in the XW Power Distribution Panel

Torque Value

Ft-lbs

N-m

15

20.4

Important:

The grounding requirements vary by country and by application. All installations

must comply with national and local codes. Consult local and national codes for specific grounding
and bonding requirements for the desired installation.

Important:

Installers must make allowance for the amount of power that can

be fed into a distribution panel and the means and location for feed-in, in
accordance with NEC 2005 article 690.64 or similar requirements of the local
electrical code.

This manual is related to the following products: