XW System Accessories Installation
5–12
975-0239-01-01
Connecting the Generator
To connect the XW Automatic Generator Start to a generator, you must identify the start
wiring configuration of the generator you want to use. Generators must be auto-start
capable, and generators equipped with remote operation connections are ideal.
If the generator is equipped for remote operation, you must examine the wiring of the
remote cable and connector (or read your generator’s documentation, if available) and
identify the following wires:
•
Ground
•
Start
•
Stop
•
Generator run signal, also known as the Hour Meter or Switched B+ (battery positive)
Wiring
requirements
To wire the XW Automatic Generator Start to the generator, you need #16 or #18 AWG
wire connected between contacts 12 to 20 on the wiring harness. How many of these wires
you connect and in which combination depends on your generator type.
Generator types
The XW Automatic Generator Start has 13 preset generator configurations, or “Gen
Types” (see the XW Automatic Start Owner’s Guide for details on Generator Types). To
ensure that the XW Automatic Generator Start is compatible with your generator’s starting
circuitry, you must select your type of generator from the XW Automatic Generator Start
menu on the XW System Control Panel after completing the installation.
7
External manual on input
White/Green
8
External manual off input
White/Red
9
External ON/OFF LED Indicator output
White/Blue
10
Constant 12/24 V B+ (battery positive) for External ON/OFF/LED
Indicator
Red
11
External ON/OFF/LED Indicator return (connected internally to
wire number 13)
Black
12
Generator run signal (switched B+) sense input
Violet
13
Generator run signal (switched B+) sense return (generator battery
negative)
Black
14
Relay 1 (Generator run/stop) Normally open contact
Blue
15
Relay 1 (Generator run/stop) Normally closed contact
White/Violet
16
Relay 1 (Generator run/stop) Common contact
Gray
17
Relay 2 (Generator start) Normally open contact
White
18
Relay 2 (Generator start) Common contact
Gray
19
Relay 3 (Preheat/cooldown) Normally open contact
Brown
20
Relay 3 (Preheat/cooldown) Common contact
Gray
Table 5-3 Contact Numbers and Functions (Continued)
Wire
Number
Function
Wiring Harness
Wire Color