York H*RC018 THRU 060 User Manual
Page 5
036-21137-003 Rev. A (1102)
Unitary Products Group
5
FOOTNOTES:
1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.
2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.
PROCEDURES:
6. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of
interconnecting line tubing.
7. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
8. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
9. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
10.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase
Outdoor Unit
H1RC036S
H1RC048S
H1RC060S
Unit Orifice (s)
1
—
—
—
Factory R-22 Charge, lbs-oz
6 - 2
7 - 10
9 - 3
Indoor Coil
Coil Orifice
TVX Kit
2
= Additional Charge, Oz
3
G2FD035S(H)14
65
702 + 0
—
—
G2FD036S(H)17,21
75
702 + 3
—
—
G2FD042S(H)21
78
702 + 0
—
—
G2FD046S(H)17
78
702 + 9
703 + 0
—
G2FD048S(H)21,24
84
702 + 17
703 + 9
—
G2FD060S(H)24
90
—
703 + 0
703 + 20
G2FD061H24
90
—
703 + 6
703 + 25
G1FA/G1UA036S14
73
702 + 1
—
—
G1FA/G1UA036S17,21
73
702 + 0
—
—
G1FA/G1UA048S17
84
—
703 + 2
—
G1FA/G1UA048S21,24
84
702 + 9
703 + 7
—
G1FA/G1UA060S21,24
90
—
703 + 14
703 + 20
G1NA036S17L
71
702 + 0
—
—
G1NA048S21D
78
702 + 0
703 + 0
—
G1NA048S24P
78
702 + 0
703 + 0
—
G1NA060S24T
87
—
—
703 + 0
G1NF036SOF
67
702 + 0
—
—
G1NF048SOF
78
—
702 + 0
—
G1NF060SOF
87
—
—
703 + 0
G1HD036
69
702 + 5
—
—
G1HD048
81
702 + 11
703 + 0
—
G1HD060
93
—
703 + 0
703 + 20
1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.
2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.