Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H1RC048S(25,46)

INDOOR COIL MODEL NO.

G1FA048S21

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1400

1600

1750

ID DB (°F)

85

80

75

70

85

80

75

70

85

80

75

70

ID WB (°F)

72

67

63

57

72

67

63

57

72

67

63

57

75

T.C.

53.4

48.9

45.1

40.2

54.3

49.8

45.9

41.3

54.9

50.3

46.4

41.8

S.C.

32.2

32.3

31.0

32.5

34.0

34.0

32.7

34.7

35.2

35.3

33.9

35.9

KW

3.81

3.64

3.49

3.32

3.86

3.68

3.53

3.37

3.88

3.71

3.56

3.39

85

T.C.

52.0

47.5

43.7

39.2

52.7

48.3

44.5

40.0

53.2

48.7

45.2

40.5

S.C.

32.2

32.3

31.1

32.7

34.1

34.1

32.8

34.7

35.4

35.5

34.5

36.0

KW

4.11

3.92

3.75

3.56

4.16

3.97

3.80

3.60

4.19

4.00

3.83

3.63

95

T.C.

49.0

44.9

41.3

36.9

49.6

45.5

42.0

37.6

50.0

45.8

42.4

38.3

S.C.

31.6

31.6

30.4

31.8

33.5

33.7

32.4

33.8

34.9

35.0

33.7

35.6

KW

4.40

4.19

4.00

3.80

4.44

4.23

4.06

3.85

4.48

4.27

4.09

3.88

105

T.C.

45.6

41.6

38.4

34.3

46.0

42.2

39.0

35.0

46.2

42.5

39.3

36.2

S.C.

30.5

30.6

29.5

30.9

32.6

32.8

31.5

32.8

34.1

34.2

32.7

34.5

KW

4.67

4.45

4.25

4.03

4.72

4.49

4.30

4.09

4.74

7.53

4.34

4.18

115

T.C.

41.8

38.3

35.3

31.7

42.3

38.8

35.8

33.0

42.5

39.0

36.2

33.5

S.C.

29.3

29.5

28.2

29.6

31.6

31.4

30.1

31.5

33.0

32.9

31.5

32.0

KW

4.91

4.67

4.47

4.25

4.94

4.73

4.52

4.36

4.98

4.76

4.56

4.41

125

T.C.

38.0

35.0

32.3

29.1

38.6

35.4

32.7

31.0

38.8

35.5

33.2

30.8

S.C.

28.1

28.4

26.9

28.3

30.6

30.0

28.7

30.2

31.9

31.6

30.4

29.5

KW

5.15

4.89

4.69

4.47

5.16

4.97

4.74

4.63

5.22

1.99

4.78

4.64

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

N1AHC1646

G2FD048(S,H)21

1.00

1.00

0.98

N1AHD2046

G2FD060(S,H)24

1.03

1.03

0.99

N1AHD2046

G2FD061

H

24

1.04

1.04

1.00

G1FA060S21,24

1.03

1.03

0.99

G2FD046(S,H)17

0.98

0.98

1.02

G2FD048(S,H)21,24

1.00

1.00

0.98

G2FD060(S,H)24

1.03

1.03

0.99

G2FD061

H

24

1.04

1.04

1.00

G1HD048

0.99

0.99

0.98

G1HD060

1.02

1.07

0.99

G1NA048S21D

1.01

1.01

0.99

G1UA048S17

0.98

0.98

1.02

G1UA048S21

1.00

1.00

1.00

G1UA060S21,24

1.03

1.03

0.99

Variable Speed

Furnace

Coil

T.C.

S.C.

KW

P1DUC20V

G1FA048S21

1.00

1.00

0.98

P1DUC20V

G2FD048(S,H)21

1.00

1.00

0.96

P1XUC16V

G1FA048S21

0.99

0.99

0.99

P1XUC16V

G2FD048(S,H)21

0.99

0.99

0.98

P1XUC20V

G1FA048S21

1.00

1.00

0.99

P1XUC20V

G2FD048(S,H)21

1.00

1.00

0.97

P1XUD20V

G1FA060S24

1.03

1.03

0.98

P1XUD20V

G2FD048(S,H)24

1.00

1.00

0.97

P1XUD20V

G2FD060(S,H)24

1.03

1.03