Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H2RC024S06
INDOOR COIL MODEL NO.
G1FA036S17,21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
600
800
1000
ID DB (°F)
85
80
75
85
80
75
85
80
75
ID WB (°F)
72
67
63
72
67
63
72
67
63
75
T.C.
25.4
24.2
22.5
25.6
24.5
23.2
25.8
24.9
23.9
S.C.
14.6
14.6
13.8
15.4
15.6
15.4
16.3
16.6
17.1
KW
1.61
1.60
1.59
1.61
1.60
1.59
1.62
1.61
1.60
85
T.C.
24.9
23.6
21.4
25.1
23.9
22.2
25.3
24.2
23.0
S.C.
14.8
14.7
13.8
15.9
16.1
15.6
17.0
17.5
17.5
KW
1.75
1.74
1.71
1.76
1.75
1.73
1.78
1.76
1.74
95
T.C.
24.4
23.0
20.3
24.6
23.2
21.2
24.8
23.5
22.2
S.C.
14.9
14.7
13.7
16.3
16.6
15.8
17.7
18.4
17.9
KW
1.90
1.88
1.84
1.92
1.89
1.86
1.93
1.90
1.88
105
T.C.
22.9
20.8
18.2
23.3
21.4
19.1
23.8
22.0
20.0
S.C.
14.5
13.8
12.9
16.3
16.0
15.0
18.1
18.1
17.2
KW
2.04
2.01
1.96
2.07
2.02
1.98
2.09
2.04
2.00
115
T.C.
21.3
18.6
16.2
22.0
19.5
17.0
22.8
20.5
17.7
S.C.
14.0
12.9
12.0
16.3
15.3
14.2
18.6
17.8
16.4
KW
2.19
2.13
2.08
2.22
2.16
2.10
2.25
2.18
2.12
125
T.C.
19.8
16.4
14.2
20.7
17.6
14.9
21.8
19.0
15.4
S.C.
13.5
12.0
11.1
16.3
14.6
13.4
19.1
17.5
15.6
KW
2.34
2.25
2.20
2.37
2.30
2.22
2.41
2.32
2.24
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2RP/F2FP024
0.99
1.01
1.00
F2RP/F2FP030
1.00
1.03
1.00
F2RC/F2FC024
0.98
1.01
1.00
F2RC/F2FC030
0.98
1.01
0.99
N1AHB0806
G2FD024(S,H)17
0.99
0.98
0.99
N1AHB0806
G2FD030(S,H)17
1.00
1.00
1.00
N1VSB12
G2FD024(S,H)17
0.99
1.05
0.92
N1VSB12
G2FD036(S,H)17
1.05
1.17
0.94
G1FA024S14,17
0.96
0.95
1.00
G1FA030S14
0.99
0.98
0.99
G1FA036S14
1.01
1.02
1.00
G1HD024
1.00
0.99
1.01
G1HD036
1.03
1.04
1.00
G1NA030S17K
1.00
1.00
1.00
G1NA030S21M
1.00
1.00
1.00
G1UA024S14,17
0.96
0.95
1.00
G1UA030S14
0.99
0.98
0.99
G1UA036S14
1.01
1.02
1.00
G1UA036S17,21
1.00
1.00
1.00
G2FD024(S,H)14,17
0.99
0.98
0.99
G2FD030(S,H)17
1.00
1.00
1.00
G2FD035(S,H)14
1.00
1.00
1.00
G2FD036(S,H)17
1.03
1.03
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P1DUA12V
G1FA024S14
0.98
0.97
0.93
P1DUA12V
G2FD024(S,H)14
1.00
1.00
0.92
P1XDB12V
G2FD024(S,H)17
1.01
1.01
0.94
P1XUB12V
G1FA024S17
0.98
0.98
0.93
P1XUB12V