036-21137-003 Rev. A (1102)

4

Unitary Products Group

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of

interconnecting line tubing.

2. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.

G1NA060S24T

78

703 + 12

G1NF024SOF

63

G1NF036SOF

67

59 + 12

63 + 0

73 + 7

701 + 12

701 + 0

702 + 7

G1NF048SOF

78

78 + 21

87 + 6

702 + 21

703 + 6

G1NF060SOF

87

87 + 18

703 + 18

703 + 0

F2RP024N06

61

53 + 4

59 + 4

701 + 4

701 + 4

F2RP030N06

65

59 + 6

63 + 4

701 + 6

701 + 4

F2RP036N06

75

63 + 4

73 + 8

701 + 4

702 + 8

F2RP042N06

78

73 + 13

78 + 0

702 + 13

702 + 0

F2FP048N06

84

73 + 16

78 + 10

87 + 11

702 + 16

702 + 10

703 + 11

F2FP060N06

90

87 + 15

703 + 15

703 + 20

F2FV060N06

90

87 + 15

703 + 15

703 + 20

FOOTNOTES:

1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.
2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)

Outdoor Unit

H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC042S06 H2RC048S06 H3RC060S06

Unit Orifice (s)

1

53

59

63

73

78

87

Factory R-22 Charge, lbs-oz.

4 - 9

4 - 7

5 - 8

5 - 3

6 - 13

7 - 7

9 - 0

Indoor Coil

Coil Orifice

Orifice or TXV Kit

2

- Additional Charge, Oz.

3