Cooling capacities, 6 ton (dce / dcg072) – York Sunline 2000 User Manual
Page 7

COOLING CAPACITIES -
6 TON (DCE / DCG072)
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
105
°
F
115
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2700
72
76
7.1
61
53
45
38
30
-
-
75
7.9
59
51
43
36
28
-
-
67
71
7.1
70
66
58
50
43
35
27
65
7.8
65
64
56
48
41
33
25
62
64
7.0
64
64
64
56
49
41
34
57
7.8
57
57
57
50
42
34
27
57
64
7.0
64
64
64
56
49
41
34
57
7.7
57
57
57
50
42
34
27
2550
72
76
7.1
59
51
44
37
29
-
-
76
7.9
57
49
42
35
27
-
-
67
71
7.1
69
64
56
49
42
34
27
66
7.9
66
61
54
47
40
32
25
62
64
7.0
64
64
64
56
49
42
35
58
7.8
58
58
58
51
43
36
29
57
64
7.0
64
64
64
56
49
42
34
58
7.7
58
58
58
50
43
36
29
2400
72
75
7.1
56
49
43
36
29
-
-
76
8.0
55
48
41
34
27
-
-
67
70
7.1
68
61
54
48
41
34
27
66
7.9
66
59
52
45
38
32
25
62
64
7.0
64
64
63
56
49
42
35
59
7.8
59
59
59
52
45
38
31
57
64
7.0
64
64
63
56
49
42
35
59
7.7
59
59
58
51
44
37
30
2100
72
73
7.1
52
45
39
33
27
-
-
73
7.9
50
44
37
31
25
-
-
67
68
7.1
63
56
50
44
38
32
26
63
7.8
61
54
48
42
36
30
24
62
61
7.0
61
61
58
52
46
40
34
56
7.7
56
56
54
48
42
35
29
57
61
7.0
61
61
58
52
46
40
34
56
7.7
56
56
53
47
41
35
29
1800
72
70
7.1
47
41
36
31
25
-
-
69
7.8
45
40
34
29
23
-
-
67
65
7.0
57
51
46
41
35
30
25
60
7.8
55
49
44
39
33
28
23
62
59
7.0
59
58
54
48
43
38
32
53
7.7
53
53
49
44
39
33
28
57
59
6.9
59
58
53
48
43
37
32
53
7.6
53
53
49
44
38
33
27
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the
motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36 KW. Refer to the Blower Performance
Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
85
°
F
95
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2700
72
80
5.7
63
55
47
40
32
-
-
77
6.3
63
55
47
40
32
-
-
67
80
5.7
76
68
60
53
45
37
30
77
6.3
75
68
60
53
45
37
30
62
70
5.5
70
70
70
62
55
47
39
71
6.3
71
71
71
63
56
48
40
57
68
5.6
68
68
68
60
52
45
37
71
6.3
71
71
71
63
56
48
40
2550
72
82
5.7
60
53
46
38
31
-
-
76
6.3
60
53
46
39
31
-
-
67
82
5.7
73
65
58
51
43
36
29
76
6.3
73
66
58
51
44
36
29
62
71
5.5
71
71
70
62
55
48
41
70
6.3
70
70
69
62
55
48
40
57
69
5.6
69
69
69
62
55
47
40
70
6.3
70
70
70
62
55
48
40
2400
72
83
5.7
58
51
44
37
30
-
-
75
6.3
58
51
44
37
30
-
-
67
83
5.7
70
63
56
49
42
35
28
75
6.3
70
64
57
50
43
36
29
62
73
5.5
73
73
70
63
56
49
42
69
6.3
69
69
68
61
54
47
40
57
71
5.6
71
71
71
64
57
50
43
69
6.3
69
69
68
61
54
47
40
2100
72
79
5.7
54
48
41
35
29
-
-
73
6.3
53
47
41
35
29
-
-
67
79
5.7
65
59
53
47
40
34
28
73
6.3
65
59
52
46
40
34
28
62
69
5.5
69
69
66
60
54
47
41
67
6.3
67
66
63
57
51
45
38
57
67
5.6
67
67
67
61
54
48
42
67
6.3
67
66
63
57
51
45
39
1800
72
74
5.6
50
44
39
34
28
-
-
71
6.3
49
43
38
33
27
-
-
67
74
5.6
60
55
50
44
39
34
28
71
6.3
59
54
48
43
38
32
27
62
65
5.4
65
65
62
57
51
46
41
65
6.2
65
63
58
53
47
42
37
57
63
5.5
63
63
63
58
52
47
42
65
6.3
65
63
58
53
47
42
37
NOMINAL RATING
530.18-TG1Y
Unitary Products Group
7