ELECTRICAL DATA

-

Cooling / Electric Heating (DCE060 & 072) with Belt-Drive

MODEL

DCE

POWER
SUPPLY

HEATER

ACCESSORY

MODEL

NUMBER

SUPPLY

AIR

BLOWER

MOTOR

FLA

ELECTRIC HEATERS

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE
SIZE

1

AMPS

MAX.

SIZE

HACR

2

BREAKER

AMPS

KW

STAGES

TOTAL

AMPS

060

208-1-60

2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006

8.6

4.0
5.6
8.0

11.9
15.9
22.2

1
1
1
2
2
2

19.1
27.1
38.3
57.4
76.6

106.9

46.0
46.0
58.6
82.5

106.4
144.4

70
70
70
90

110
150

70
70
70
90

110
150

230-1-60

2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006

8.6

5.3
7.5

10.6
15.9
21.2
29.6

1
1
1
2
2
2

22.1
31.3
44.2
66.3
88.3

123.3

46.0
49.8
66.0
93.6

121.2
164.9

70
70
70

100
125
175

70
70
70

100
125
175

208-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025
2CE04503025

6.0

4.0
5.6
8.0

11.9
15.9
22.2

1
1
1
2
2
2

11.0
15.6
22.1
33.1
44.2
61.7

27.3
27.3
35.1
48.9
62.7
84.6

40
40
40
50
70
90

40
40
40
50
70
90

230-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025
2CE04503025

6.0

5.3
7.5

10.6
15.9
21.2
29.6

1
1
1
2
2
2

12.7
18.0
25.5
38.2
51.0
71.2

27.3
30.1
39.4
55.3
71.2
96.5

40
40
40
60
80

100

40
40
40
60
80

100

460-3-60

2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*
2CE04503046*

3.0

6.8

10.1
13.6
19.5
28.8

1
1
1
2
2

8.2

12.1
16.4
23.5
34.6

14.0
18.9
24.2
33.1
47.1

20
20
25
35
50

20
20
25
35
50

575-3-60

2CE04501058
2CE04501558
2CE04502058
2CE04503058

2.4

10.6
15.9
21.2
30.4

1
1
2
2

10.2
15.3
20.4
29.3

15.7
22.1
28.5
39.6

20
25
30
40




072

208-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025
2CE04503025

7.3

4.0
5.6
8.0

11.9
15.9
22.2

1
1
1
2
2
2

11.0
15.6
22.1
33.1
44.2
61.7

34.0
34.0
36.7
50.6
64.4
86.3

50
50
50
60
70
90

50
50
50
60
70
90

230-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025
2CE04503025

7.3

5.3
7.5

10.6
15.9
21.2
29.6

1
1
1
2
2
2

12.7
18.0
25.5
38.2
51.0
71.2

34.0
34.0
41.0
56.9
72.9
98.1

50
50
50
60
80

100

50
50
50
60
80

100

460-3-60

2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*
2CE04503046*

3.7

6.8

10.1
13.6
19.5
28.8

1
1
1
2
2

8.2

12.1
16.4
23.5
34.6

17.3
19.8
25.1
33.9
47.9

25
25
30
35
50

25
25
30
35
50

575-3-60

2CE04501058
2CE04501558
2CE04502058
2CE04503058

2.8

10.6
15.9
21.2
30.4

1
1
2
2

10.2
15.3
20.4
29.3

16.2
22.6
29.0
40.1

20
25
30
45




1

Dual element, time delay type

2

Standard circuit breakers may be used in Canada and on applications

over 60 amps where the heaters are separately fused.

* These electric heaters DO NOT include a fuse box. If a fuse box is
required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation.

Electric Heat

Correction

Factors

Nominal Voltage

Voltage

KW Cap

Multipier

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

Fuse Block

2FB04700425

208/240 Volts

2FB04700546

460 Volts

530.18-TG1Y

Unitary Products Group