Unit dimensions, Dce and dcg - 3, 4, 5 & 6 ton) – York Sunline 2000 User Manual

Page 17

background image

Front

DCE Units

24"

DCG Units

32"

Back

12" (Less Economizer)

36" (With Economizer

or Fixed Air/Motorized

Damper)

Left Side

(Filter Access)

24"(Less Economizer)

36" (With Economizer)

Right Side

(Cond. Coil)

24"

Below Unit

1

2

0"

Above Unit

2

72" (For Condenser

Air Discharge)

1 Units may be installed on combustible floors made from
wood or class A, B or C roof covering material.

2

Units must be installed oudoors. Overhanging structures

or shrubs should not obstruct condenser air discharge outlet.

NOTES:
DCE Models: Units and ductwork are approved for zero clearance to
combustible materials when equipped with electric heaters.

DCG Models: A 1" clearance must be provided between any combusti-
ble material and the supply air ductwork for a
distance of 3 feet from the unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).

Four (4) feet below, 4 horizontal feet from, or 1 foot above
any door or gravity air inlet into the building.

Four (4) feet from electric meters, gas meters, regualtors
and relief equipment.

HOLE

KNOCKOUT

SIZE

(DIA.)

USED FOR

A

7/8" *

Control Wiring

(Side or Bottom)**

B

2" *

Power Wiring

(Side or Bottom)

C

1-5/8"

Gas Piping (Front)

D

1-1/2"

Gas Piping (Bottom)

*

Knockouts in the bottom of the unit can be located by the

slice in the insulation.

**

Do not remove the 2" knockout ring.

UTILITIES ENTRY DATA

UNIT DIMENSIONS

(DCE AND DCG - 3, 4, 5 & 6 TON)

RETURN AIR

SUPPLY AIR

CONDENSER AIR

OUTDOOR AIR
(Economizer)

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
(Direct-Drive units)

SCROLL
COMPRESSOR
ACCESS

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
(Direct-Drive units)

GAS SUPPLY ENTRY
(

1

2

“ NPTI AT GAS VALVE)

GAS SUPPLY ENTRY
(

1

2

“ NPTI AT GAS VALVE)

SCROLL COMPR.
ACCESS

CLEARANCES

All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.

530.18-TG1Y

Unitary Products Group

17