beautypg.com

Ratings, Physical data, Sound power ratings for supply air blower – York Sunline 2000 User Manual

Page 3: Basic units

background image

MODEL

ARI RATINGS

1

GAS HEAT CAPACITY

STANDARD

CFM

COOLING CAPACITY

80 / 67-95

°

F

SOUND

RATING

2

(dbels)

INPUT

(MBH)

OUTPUT

(MBH)

AFUE

(%)

S.S.E.

(%)

TEMP.

RISE

(

°

F)

GAS

LINE SIZE

(in. OD)

MBH

SEER

EER

DCG036N040
DCG036N079

36.0
36.0

10.00
10.00

9.10
9.10

82
82

50

100

40
79

80.9
80.5

81.6
80.8

15-45
40-70

1

2

1

2

1.300

DCG048N060
DCG048N099

47.4
47.4

10.00
10.00

9.00
9.00

82
82

75

125

59
99

80.9
80.3

81.6
80.6

25-55
45-75

1

2

1

2

1.700

DCG060N079
DCG060N099

59.0
59.0

10.00
10.00

9.10
9.10

82
82

100
125

79
99

80.5
80.3

80.8
80.6

25-55
35-65

1

2

1

2

2.100

DCG072N079
DCG072N099

72.0

4

72.0

4

-
-

9.00
9.00

84
84

100
125

79
99

80.5
80.3

80.8
80.6

25-55
35-65

1

2

1

2

2.400

1

Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2

Rated in accordance with ARI Standard 270.

3

Heaters are available as accessories - all with single

point power supply.

4

Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
EER = Energy Efficiency Ratio - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
S.S.E. = Steady State Efficiency. (Percent Output).

RATINGS

MODEL

ARI RATINGS

1

NOMINAL

ELECTRIC HEAT CAPACITY

3

(KW)

STANDARD

CFM

COOLING CAPACITY

80 / 67-95

°

F

SOUND

RATING

2

(dbels)

MBH

SEER

EER

240V

480V

600V

DCE036

36.0

10.00

9.10

82

5, 7, 10,

15 & 20

7, 10,

15 & 20

10,

15 & 20

1.300

DCE048

47.4

10.00

9.00

82

5, 7, 10,

15 & 20

7, 10,

15 & 20

10,

15 & 20

1.700

DCE060

59.0

10.00

9.10

82

5, 7, 10,

15, 20 & 30

7, 10, 15

20 & 30

10, 15,

20 & 30

2.100

DCE072

72.0

-

9.00

84

5, 7, 10,

15, 20 & 30

7, 10, 15,

20 & 30

10, 15,

20 & 30

2.400

CAPACITY RATINGS - Cooling / Gas Heating

CAPACITY RATINGS - Cooling / Electric Heating

= Not ARI Listed.

PHYSICAL DATA -

BASIC UNITS

MODEL

EVAPORATOR

BLOWER

EVAPORATOR

COIL

COMPRESSOR

TYPE

CONDENSER

FAN

CONDENSER

COIL

AIR

FILTERS

(SEE NOTE)

CHARGE

CENT

RI

F

U

GAL

(D

ia

.

x

W

d

. i

n

.)

F

A

N M

O

T

O

R

HP

(D

IR

ECT

-DRIVE)

F

A

N M

O

T

O

R

HP

(BEL

T-

DRIVE)

R

O

W

S

DEEP

F

INS PER

INCH

F

A

CE AREA

(S

q.

F

t.)

HERM

ET

ICALL

Y

SEAL

ED

PR

O

PEL

L

E

R

DI

A.

(i

n.)

F

A

N M

O

T

O

R

HP

NOM

. CF

M

T

O

T

A

L

R

O

W

S

DEEP

F

INS PER

INCH

F

A

CE AREA

(S

q.

F

t.)

QU

AN

TI

TY

PER UNI

T

(15"

X

20"

X

1"

)

QU

AN

TI

TY

PER UNI

T

(14"

X

25"

X

1"

)

TO

T

A

L

F

A

C

E

AREA (

s

q

.

ft

.)

REF

R

IG

ERANT

R-22 (l

bs

./

oz.

)

036

12 x 10

1

2

1

1

2

3

13

3.6

SCROLL

TYPE

24

1

4

3,400

1

16

17.1

2

1

6.3

5/8

048

12 x 10

3

4

1

1

2

3

13

4.3

24

1

4

3,400

1

16

17.1

2

1

6.3

6/8

060

12 x 10

1

1

1

2

3

13

5.1

24

1

4

3,400

1

22

17.1

2

1

6.3

6/8

072

12 x 11

1

1

1

2

4

13

5.1

24

1

4

3,300

2

16

16.7

2

1

6.3

10/0

NOTE: Filter racks are adapted for 1" or 2" thick filters.

SOUND POWER RATINGS FOR SUPPLY AIR BLOWER

MODEL

CFM

ESP

BLOWER

SOUND POWER (dB 10

-12

watts)

OCTAVE BAND CENTERLINE FREQUENCY (Hz)

SWL

dB (A)

dB (A)

@

10 ft.

*

IWG

SPEED

KW

63

125

250

500

1,000

2,000

4,000

8,000

036

1,200

0.60

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1,600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2,000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

072

2,200

0.30

HIGH

1.35

87

87

77

70

72

65

60

55

77

44

* At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for reference
only. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in
any other form than sound power level ratings.

530.18-TG1Y

Unitary Products Group

3