Cooling capacities, 3 ton (dce / dcg036) – York Sunline 2000 User Manual
Page 4

COOLING CAPACITIES -
3 TON (DCE / DCG036)
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
105
°
F
115
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1750
72
41
3.7
34
29
25
20
16
-
-
39
4.1
33
28
24
19
15
-
-
67
38
3.7
38
37
33
28
24
19
15
36
4.0
36
36
32
27
23
18
14
62
34
3.7
34
34
34
30
25
21
16
32
4.0
32
32
32
27
23
18
14
57
35
3.6
35
35
35
31
26
22
17
33
4.0
33
33
33
28
24
19
15
1475
72
40
3.7
30
26
23
19
15
-
-
38
4.1
30
26
22
18
14
-
-
67
37
3.6
36
34
30
26
22
18
14
35
4.0
34
33
29
25
21
17
13
62
33
3.7
33
33
33
29
25
21
17
31
4.0
31
31
31
27
23
19
15
57
34
3.6
34
34
34
30
26
22
18
32
4.0
32
32
32
28
24
20
16
1200
72
39
3.7
27
24
20
17
14
-
-
37
4.1
26
23
20
16
13
-
-
67
36
3.6
34
30
27
24
20
17
14
34
4.0
33
30
26
23
20
16
13
62
32
3.6
32
32
32
29
25
22
19
30
4.0
30
30
30
27
24
20
17
57
33
3.6
33
33
33
29
26
23
19
31
3.9
31
31
31
27
24
21
17
1050
72
37
3.6
25
22
19
16
13
-
-
36
4.1
24
21
18
15
12
-
-
67
35
3.6
31
28
25
22
19
16
13
32
4.0
30
27
24
21
18
15
12
62
31
3.6
31
31
29
27
24
21
18
29
4.0
29
29
28
25
22
19
16
57
32
3.5
32
32
30
27
24
21
18
30
3.9
30
29
28
25
22
19
16
900
72
36
3.6
22
20
17
15
12
-
-
34
4.0
21
19
16
14
11
-
-
67
33
3.6
28
25
23
20
18
15
13
31
4.0
27
24
22
19
17
14
11
62
30
3.6
30
29
27
24
22
19
17
28
4.0
28
28
25
22
20
17
15
57
31
3.5
31
30
28
25
22
20
17
28
3.9
28
28
25
23
20
17
15
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the
motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36 KW. Refer to the Blower Performance
Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
85
°
F
95
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1750
72
45
3.1
35
30
26
21
17
-
-
43
3.3
35
30
26
21
17
-
-
67
43
3.0
43
38
34
29
25
20
16
41
3.3
41
38
34
29
25
21
16
62
39
3.0
39
39
39
34
30
25
21
36
3.3
36
36
36
32
27
23
18
57
40
2.9
40
40
40
35
31
26
22
38
3.2
38
38
38
33
29
24
20
1475
72
44
3.1
31
28
24
20
16
-
-
42
3.3
31
27
23
20
16
-
-
67
41
3.0
39
35
31
27
23
19
16
39
3.3
37
35
31
27
23
19
15
62
38
3.0
38
38
37
33
29
25
21
36
3.3
36
36
35
31
27
23
19
57
39
2.9
39
39
39
35
31
27
23
37
3.2
37
37
36
32
28
25
21
1200
72
42
3.1
28
25
22
18
15
-
-
41
3.3
28
24
21
18
14
-
-
67
40
3.0
35
32
28
25
22
18
15
38
3.2
34
31
28
25
21
18
15
62
36
3.0
36
36
35
31
28
25
21
35
3.3
35
35
34
30
27
24
20
57
37
2.9
37
37
37
34
31
27
24
36
3.2
36
36
35
32
28
25
22
1050
72
41
3.1
26
23
20
17
14
-
-
39
3.2
26
23
20
17
14
-
-
67
38
3.0
32
30
27
24
21
18
15
37
3.2
32
29
26
23
20
17
14
62
35
3.0
35
35
33
30
27
24
21
33
3.2
33
33
31
28
25
22
20
57
36
2.9
36
36
35
32
29
26
23
34
3.2
34
34
32
30
27
24
21
900
72
39
3.1
24
21
19
16
14
-
-
38
3.2
23
21
18
16
13
-
-
67
37
3.0
30
27
25
22
20
17
15
36
3.2
29
26
24
21
19
16
14
62
34
3.0
34
33
30
28
25
23
20
32
3.2
32
31
29
26
24
21
19
57
34
2.9
34
34
33
30
27
25
22
33
3.1
33
33
30
27
25
22
20
NOMINAL RATING
530.18-TG1Y
4
Unitary Products Group