beautypg.com

29 wr electrical data - standard drive, Motor with powered conv. outlet – York SUNLINE MAGNADRY WR 180 User Manual

Page 42

background image

262292-YTG-B-0107

42

Unitary Products Group

NOTE 1: HACR Type per NEC.

TABLE 29: WR ELECTRICAL DATA - STANDARD DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET

MODEL

(TONNAGE)

VOLTAGE

COMPRESSORS

OD FAN

MOTORS

FLA EACH

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

AMPS

HEATER OPTION

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

MODEL

KW

STAGES

AMPS

180

(15)

208

22.4

164

2.1

17.7

10.0

None

-

-

-

86.5

100

E18

13.5

1

37.5

86.5

100

E36

27

2

74.9

128.3

150

E54

40.6

2

112.7

175.5

200

E72

54.1

2

150.2

184.8

200

230

22.4

164

2.1

16.4

10.0

None

-

-

-

85.2

100

E18

18.0

1

43.3

87.1

100

E36

36.0

2

86.6

141.3

150

E54

54.0

2

129.9

162.9

175

E72

72.0

2

173.2

206.2

225

460

10.9

100

1.2

8.2

5.0

None

-

-

-

42.5

50

E18

18.0

1

21.7

43.6

50

E36

36.0

2

43.3

70.6

80

E54

54.0

2

65.0

81.5

90

E72

72.0

2

86.6

103.1

110

575

8.3

78

0.9

6.6

4.0

None

-

-

-

32.9

40

E18

18.0

1

17.3

34.9

40

E36

36.0

2

34.6

56.6

60

E54

54.0

2

52.0

65.2

70

E72

72.0

2

69.3

82.5

90

240

(20)

208

30.1

225

2.4

24.2

10.0

None

-

-

-

111.5

125

E18

13.5

1

37.5

111.5

125

E36

27

2

74.9

136.4

150

E54

40.6

2

112.7

183.6

200

E72

54.1

2

150.2

192.9

200

230

30.1

225

2.4

24.2

10.0

None

-

-

-

111.5

125

E18

18.0

1

43.3

111.5

125

E36

36.0

2

86.6

151.0

175

E54

54.0

2

129.9

172.7

175

E72

72.0

2

173.2

216.0

225

460

15.5

114

0.9

12.1

5.0

None

-

-

-

55.6

70

E18

18.0

1

21.7

55.6

70

E36

36.0

2

43.3

75.5

80

E54

54.0

2

65.0

86.3

90

E72

72.0

2

86.6

108.0

110

575

12.1

80

0.6

10.3

4.0

None

-

-

-

43.9

50

E18

18.0

1

17.3

43.9

50

E36

36.0

2

34.6

61.2

70

E54

54.0

2

52.0

69.8

70

E72

72.0

2

69.3

87.2

90

300

(25)

208

42.3

245

2.4

38.6

10.0

None

-

-

-

153.4

175

E18

13.5

1

37.5

153.4

175

E36

27

2

74.9

154.4

175

E54

40.6

2

112.7

201.6

225

E72

54.1

2

150.2

210.9

225

230

42.3

245

2.4

38.6

10.0

None

-

-

-

153.4

175

E18

18.0

1

43.3

153.4

175

E36

36.0

2

86.6

169.0

175

E54

54.0

2

129.9

190.7

225

E72

72.0

2

173.2

234.0

250

460

17.6

125

0.9

19.3

5.0

None

-

-

-

67.9

80

E18

18.0

1

21.7

67.9

80

E36

36.0

2

43.3

84.5

90

E54

54.0

2

65.0

95.3

110

E72

72.0

2

86.6

117.0

125

575

14.5

100

0.6

16.2

4.0

None

-

-

-

55.7

70

E18

18.0

1

17.3

55.7

70

E36

36.0

2

34.6

68.6

70

E54

54.0

2

52.0

77.2

90

E72

72.0

2

69.3

94.5

100

VOLTAGE LIMITATIONS

ELECTRIC HEAT CORRECTION FACTORS

POWER SUPPLY

VOLTAGE

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

MIN.

MAX.

208

208

1.00

VOLTAGE

LIMITATIONS

1

208/230-3-60

187

253

240

230

0.92

460-3-60

414

506

480

460

0.92

575-3-60

518

630

600

575

0.92

1.

Utilization Range “A” in accordance with ARI Standard 110.