28 wr electrical data - low airflow drive, Motor w/o powered conv. outlet – York SUNLINE MAGNADRY WR 180 User Manual
Page 41
262292-YTG-B-0107
Unitary Products Group
41
NOTE 1: HACR Type per NEC.
TABLE 28: WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET
MODEL
(TONNAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
240
(20)
208
30.1
225
2.4
20.0
0.0
None
0.0
-
-
97.3
125
E18
13.5
1
37.5
97.3
125
E36
27.0
2
75.1
118.7
125
E54
40.6
2
112.7
165.9
175
E72
54.1
2
150.2
175.2
200
230
30.1
225
2.4
20.0
0.0
None
0.0
-
-
97.3
125
E18
18.0
1
43.3
97.3
125
E36
36.0
2
86.6
133.3
150
E54
54.0
2
129.9
154.9
175
E72
72.0
2
173.2
198.2
225
460
15.5
114
0.9
10.0
0.0
None
0.0
-
-
48.5
60
E18
18.0
1
21.7
48.5
60
E36
36.0
2
43.3
66.6
70
E54
54.0
2
65.0
77.5
90
E72
72.0
2
86.6
99.1
110
575
12.1
80
0.6
7.5
0.0
None
0.0
-
-
37.1
45
E18
18.0
1
17.3
37.1
45
E36
36.0
2
34.6
52.7
60
E54
54.0
2
52.0
61.3
70
E72
72.0
2
69.3
78.7
90
300
(25)
208
42.3
245
2.4
20.0
0.0
None
0.0
-
-
124.8
150
E18
13.5
1
37.5
124.8
150
E36
27.0
2
75.1
124.8
150
E54
40.6
2
112.6
165.9
175
E72
54.1
2
150.1
175.2
200
230
42.3
245
2.4
20.0
0.0
None
0.0
-
-
124.8
150
E18
18.0
1
43.3
124.8
150
E36
36.0
2
86.6
133.3
150
E54
54.0
2
129.9
154.9
175
E72
72.0
2
173.2
198.2
225
460
17.6
125
0.9
10.0
0.0
None
0.0
-
-
53.2
70
E18
18.0
1
21.7
53.2
70
E36
36.0
2
43.3
66.6
70
E54
54.0
2
65.0
77.5
90
E72
72.0
2
86.6
99.1
110
575
14.5
100
0.6
7.5
0.0
None
0.0
-
-
42.5
50
E18
18.0
1
17.3
42.5
50
E36
36.0
2
34.6
52.7
60
E54
54.0
2
52.0
61.3
70
E72
72.0
2
69.3
78.7
90
VOLTAGE LIMITATIONS
ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
MIN.
MAX.
208
208
1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60
187
253
240
230
0.92
460-3-60
414
506
480
460
0.92
575-3-60
518
630
600
575
0.92
1.
Utilization Range “A” in accordance with ARI Standard 110.