TABLE 11: WR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
KW
BHP CFM RPM
KW
BHP CFM RPM
KW
BHP
0.2
6284
956
3.50 4.20 6080
922
3.14 3.77 5800
889
2.84 3.41 5514
856
2.536 3.04 5290
821
2.209 2.65 5056
788
1.992 2.39
0.4
5918
957
3.25 3.89 5718
923
2.92 3.51 5434
889
2.61 3.13 5228
857
2.32
2.78 4914
822
2.04
2.45 4668
789
1.85
2.22
0.6
5590
958
3.05 3.66 5379
925
2.74 3.28 5098
891
2.41 2.90 4829
858
2.18
2.61 4452
823
1.81
2.17 4175
790
1.67
2.01
0.8
5226
959
2.79 3.34 4985
926
2.45 2.95 4639
893
2.18 2.62 4336
860
1.91
2.30 3937
825
1.58
1.90 3608
791
1.42
1.70
1.0
4801
961
2.52 3.03 4529
928
2.23 2.68 4141
894
1.95 2.34 3754
861
1.69
2.03 3222
826
1.35
1.62 2752
792
1.13
1.35
1.2
4326
962
2.28 2.73 3912
930
1.95 2.34 3405
896
1.59 1.91 2964
863
1.38
1.65
-
-
-
-
-
-
-
-
1.4
3650
965
1.95 2.34 3199
931
1.62 1.95
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns
15-Ton Standard Drive, Cooling Only, Bottom Connection
1VP62 x BK105
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
External Static ("WC)
SCFM
1 Turn
2 Turns
3 Turns
5 Turns
6 Turns
4 Turns