13 wr180 blower performance - 15 ton high, Static drive (cooling only) downflow – York SUNLINE MAGNADRY WR 180 User Manual
Page 28
262292-YTG-B-0107
28
Unitary Products Group
TABLE 13: WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
KW
BHP CFM RPM
KW
BHP CFM RPM
KW
BHP
0.2
7695 1120 5.68 6.93 7434 1082 5.12 6.25 7139 1043 4.55 5.55 6853 1005
4.10
4.92 6537
966
3.614 4.34 6173
926
3.20
3.84
0.4
7344 1122 5.34 6.51 7089 1083 4.80 5.86 6791 1044 4.32 5.28 6497 1005
3.80
4.57 6157
966
3.28
3.94 5791
927
2.92
3.50
0.6
6994 1123 4.99 6.08 6751 1084 4.48 5.47 6477 1046 4.06 4.87 6190 1006
3.63
4.36 5855
967
3.25
3.90 5430
927
2.74
3.29
0.8
6711 1125 4.77 5.83 6478 1086 4.29 5.24 6196 1046 3.85 4.62 5864 1007
3.41
4.09 5434
968
2.95
3.54 5023
928
2.54
3.04
1.0
6415 1126 4.54 5.54 6193 1087 4.09 4.90 5802 1048 3.58 4.30 5449 1008
3.07
3.68 5017
969
2.71
3.25 4554
929
2.21
2.66
1.2
6032 1127 4.22 5.15 5823 1088 3.80 4.56 5418 1049 3.28 3.93 5011 1009
2.79
3.34 4554
970
2.40
2.88 4030
930
1.99
2.39
1.4
5659 1128 3.89 4.67 5463 1089 3.50 4.20 4996 1049 3.00 3.60 4549 1010
2.48
2.98 4120
970
2.09
2.51 3216
931
1.63
1.95
1.6
5315 1130 3.60 4.32 5042 1090 3.23 3.88 4481 1050 2.68 3.21 4004 1011
2.20
2.64 3222
971
1.75
2.09
-
-
-
-
1.8
4733 1131 3.15 3.78 4402 1091 2.83 3.40 3756 1052 2.28 2.73
-
-
-
-
-
-
-
-
-
-
-
-
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns
7.5 HP motor
5 HP motor
15-Ton High Static Drive, Cooling Only, Bottom Connection
1VP62 x BK90
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
External Static ("WC)
SC
FM
1 Turn
2 Turns
3 Turns
5 Turns
6 Turns
4 Turns