TABLE 12: WR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (GAS HEAT) DOWNFLOW

Blower Performance (Downflow Discharge)

ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM

KW

BHP CFM RPM

KW

BHP CFM RPM

KW

BHP

0.2

6158

956

3.29 3.95 5958

922

2.96 3.55 5684

889

2.67 3.20 5404

856

2.38

2.86 5184

821

2.08

2.49 4955

788

1.87

2.25

0.4

5800

957

3.05 3.66 5604

923

2.75 3.30 5325

889

2.45 2.94 5123

857

2.18

2.62 4816

822

1.92

2.31 4575

789

1.74

2.09

0.6

5478

958

2.87 3.44 5271

925

2.57 3.09 4996

891

2.27 2.72 4732

858

2.05

2.46 4363

823

1.70

2.04 4092

790

1.57

1.89

0.8

5121

959

2.62 3.14 4885

926

2.31 2.77 4546

893

2.05 2.46 4249

860

1.80

2.16 3858

825

1.48

1.78 3536

791

1.33

1.60

1.0

4705

961

2.37 2.85 4438

928

2.10 2.52 4058

894

1.83 2.20 3679

861

1.59

1.91 3158

826

1.27

1.52 2697

792

1.06

1.27

1.2

4239

962

2.14 2.57 3834

930

1.83 2.20 3337

896

1.49 1.79 2905

863

1.29

1.55

-

-

-

-

-

-

-

-

1.4

3577

965

1.83 2.20 3135

931

1.52 1.83

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1 turn

2 turns

3 turns

4 turns

5 turns

6 turns

15-Ton Standard Drive, Gas Heat, Bottom Connection

1VP62 x BK105

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

External Static ("WC)

SCFM

1 Turn