9 cooling capacities for wr300 (alternate, Reheat mode) – York SUNLINE MAGNADRY WR 180 User Manual

Page 20

background image

262292-YTG-B-0107

20

Unitary Products Group

TABLE 9: COOLING CAPACITIES FOR WR300 (ALTERNATE REHEAT MODE)

Air on Evaporator Coil

Temperature of Air on Condenser Coil

75°F

85°F

CFM

WB
(°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65

7500

67

140

21.1

19

17

16

14

12

10

129

22.3

12

11

9

8

7

6

62

128

19.9

88

86

84

82

80

78

119

21.1

68

67

66

65

64

62

57

117

18.8

104 102 100

98

96

94

113

20.3

81

80

79

78

77

76

7750

67

139

21.2

21

19

17

15

12

10

128

22.4

13

12

10

9

8

7

62

127

20.1

88

86

84

82

80

78

118

21.2

75

74

73

71

70

69

57

116

18.9

104 102 100

98

96

94

112

20.4

90

88

87

86

84

83

8000

67

138

21.3

22

20

18

15

13

11

127

22.5

14

13

11

10

9

7

62

126

20.2

88

86

84

82

80

78

117

21.3

82

81

79

78

76

75

57

115

19.0

104 102 100

98

96

93

111

20.4

98

96

95

93

92

91

8500

67

138

21.4

24

22

19

17

15

12

127

22.5

16

15

13

12

10

9

62

125

20.2

98

95

92

90

88

85

117

21.3

95

94

92

90

89

87

57

115

19.1

109 108 107 105 102 100

111

20.5

104 104 103 101 100

98

9000

67

137

21.4

26

23

21

19

16

14

127

22.5

18

17

15

13

12

10

62

125

20.2

107 104 100

98

96

93

117

21.3

108 107 105 103 102 100

57

114

19.1

114 114 114 112 109 107

111

20.5

111 111 111 109 107 106

95°F

105°F

7500

67

118

23.4

4

4

3

3

2

2

108

24.8

3

3

2

2

1

1

62

110

22.3

49

48

48

48

47

47

101

23.6

31

31

30

30

30

29

57

108

21.7

59

59

58

58

57

57

98

23.1

37

37

36

36

36

35

7750

67

117

23.5

5

5

4

4

3

3

107

24.9

5

4

4

3

2

2

62

109

22.3

62

62

61

61

60

60

100

23.7

51

50

50

49

48

48

57

107

21.8

75

75

74

73

73

72

97

23.2

60

59

59

58

58

57

8000

67

116

23.6

6

6

5

4

4

3

106

24.9

6

6

5

4

3

3

62

108

22.4

75

75

74

73

73

72

99

23.8

70

69

69

68

67

66

57

106

21.9

91

90

90

89

89

88

96

23.3

82

82

81

80

79

79

8500

67

117

23.6

9

8

7

6

5

5

107

24.9

8

7

6

5

4

3

62

109

22.4

93

92

92

91

90

89

100

23.8

79

79

78

77

76

75

57

107

21.9

99

99

99

98

97

96

97

23.3

87

87

86

85

84

83

9000

67

118

23.6

11

10

9

8

7

6

108

24.9

9

8

7

6

5

4

62

110

22.4

110 108 107 106 105 104

101

23.8

89

88

87

86

85

84

57

108

21.9

108 108 108 107 106 105

98

23.3

92

92

91

90

89

88

115°F

125°F

7500

67

97

26.2

-

-

-

-

-

-

87

27.6

-

-

-

-

-

-

62

91

25.0

14

13

13

12

12

12

82

26.4

-

-

-

-

-

-

57

88

24.6

15

15

15

14

14

13

77

26.0

-

-

-

-

-

-

7750

67

97

26.2

4

4

3

2

2

1

87

27.6

4

3

2

2

-

-

62

91

25.0

39

39

38

37

37

36

82

26.4

28

27

27

26

25

24

57

87

24.6

45

44

43

43

42

41

77

26.0

29

29

28

27

27

26

8000

67

96

26.3

7

6

5

4

3

2

86

27.6

7

6

5

4

-

-

62

90

25.1

65

64

63

62

62

61

81

26.5

60

59

58

57

56

55

57

86

24.7

74

73

72

71

70

69

76

26.1

65

64

63

62

61

60

8500

67

98

26.3

7

6

5

4

3

2

88

27.7

6

5

4

3

-

-

62

92

25.1

66

65

64

63

62

61

83

26.5

53

52

50

49

48

47

57

88

24.7

75

74

73

72

71

70

78

26.1

63

62

60

59

58

57

9000

67

99

26.3

7

6

5

4

3

2

90

27.7

6

4

3

2

-

-

62

93

25.1

68

66

65

64

63

62

85

26.5

47

45

43

42

40

39

57

89

24.7

77

76

74

73

72

71

80

26.1

61

59

58

56

55

54

1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity