14 wr180 blower performance - 15 ton high, Static drive (gas heat) downflow – York SUNLINE MAGNADRY WR 180 User Manual

Page 29

background image

262292-YTG-B-0107

Unitary Products Group

29

TABLE 14: WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW

Blower Performance (Downflow Discharge)

ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM

KW

BHP CFM RPM

KW

BHP CFM RPM

KW

BHP

0.2

7541 1120 5.34 6.51 7285 1082 4.81 5.87 6996 1043 4.28 5.22 6716 1005

3.85

4.63 6406

966

3.40

4.08 6050

926

3.00

3.61

0.4

7197 1122 5.02 6.12 6947 1083 4.51 5.50 6655 1044 4.06 4.88 6367 1005

3.58

4.29 6034

966

3.08

3.70 5675

927

2.74

3.29

0.6

6854 1123 4.69 5.72 6616 1084 4.21 5.14 6347 1046 3.81 4.58 6066 1006

3.41

4.09 5738

967

3.06

3.67 5321

927

2.58

3.09

0.8

6576 1125 4.49 5.48 6348 1086 4.04 4.84 6072 1046 3.62 4.35 5747 1007

3.20

3.84 5325

968

2.78

3.33 4923

928

2.38

2.86

1.0

6287 1126 4.27 5.21 6069 1087 3.84 4.61 5686 1048 3.37 4.04 5340 1008

2.88

3.46 4917

969

2.54

3.05 4463

929

2.08

2.50

1.2

5911 1127 3.97 4.76 5707 1088 3.57 4.29 5310 1049 3.08 3.69 4911 1009

2.62

3.14 4463

970

2.25

2.70 3949

930

1.87

2.24

1.4

5545 1128 3.66 4.39 5354 1089 3.29 3.95 4896 1049 2.82 3.38 4458 1010

2.33

2.80 4038

970

1.96

2.36 3152

931

1.53

1.83

1.6

5209 1130 3.38 4.06 4941 1090 3.04 3.65 4391 1050 2.51 3.02 3924 1011

2.07

2.48 3158

971

1.64

1.97

-

-

-

-

1.8

4638 1131 2.96 3.56 4314 1091 2.66 3.19 3681 1052 2.14 2.57

-

-

-

-

-

-

-

-

-

-

-

-

1 turn

2 turns

3 turns

4 turns

5 turns

6 turns

7.5 HP motor

5 HP motor

15-Ton High Static Drive, Gas Heat, Bottom Connection

1VP62 x BK90

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

External Static ("WC)

SC

F

M

1 Turn

2 Turns

3 Turns

5 Turns

6 Turns

4 Turns