York SUNLINE PLUS D2EG 048 User Manual

Page 11

background image

Unitary Products Group

11

035-14832-003-A-0204

MODEL

DEG

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

16.7

13.1

6.7

5.1

87

110

54

44

2.3

2.3

1.4

1.4

7.6

5.3

2.6

2.0

30.7

23.9

12.4

9.8

45

35

20

15

45

35

20

15

048

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

18.7

11.9

6.3

4.9

135.0

130.0

64.8

52.0

2.3

2.3

1.4

1.4

8.6

5.2

2.6

2.0

42.6

26.3

14.3

11.4

60

40

20

15

60

40

20

15

060

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

32.1

19.3

10.0

7.9

169

123

62

50

2.3

2.3

1.4

1.4

8.6

6.0

3.0

2.4

51.0

32.4

16.9

13.7

80

50

25

20

80

50

25

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.

TABLE 11 - ELECTRICAL DATA - w/Belt-DriveBlower Motor

MODEL

DEG

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

16.7

13.1

6.7

5.1

87

110

54

44

2.3

2.3

1.4

1.4

4.4

4.4

2.0

2.2

27.5

23.1

12.0

10.7

40

35

15

15

40

35

15

15

048

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

18.7

11.9

6.3

4.9

135

130

64

52.0

2.3

2.3

1.4

1.4

5.0

5.0

2.2

2.2

38.6

25.7

13.2

11.4

60

40

20

15

60

40

20

15

060

208/230-1-60

208/230-3-60

460-3-60

575-3-60

187

187

414

518

253

253

504

630

32.1

19.3

10.0

7.9

135

150

73

50

2.3

2.3

1.4

1.4

6.6

6.6

3.3

3.3

49.0

33.0

17.2

14.6

80

50

25

20

80

50

25

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.

TABLE 10 - ELECTRICAL DATA - w/Direct-DriveBlower Motor

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer

1, 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Bottom Duct Connections

1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1

Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2

The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM

during full economizer operation.

TABLE 8 - STATIC RESISTANCES

MODEL

BLOWER

RANGE

(RPM)

MOTOR*

ADJUSTABLE

MOTOR PULLEY

FIXED

BLOWER PULLEY

BELT

HP

RPM

FRAME

SIZE

SERVICE

FACTOR

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

LENGTH

(in.)

DESIG-

NATION

DEG 036

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

3.7

1

37.3

A36

DEG 048

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

1

37.3

A36

DEG 060

850 - 1220

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.2

1

37.3

A36

*

All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any

heating device.

TABLE 9 - MOTOR AND DRIVE DATA - Belt-Drive Blower