beautypg.com

Check monthly, Automatic air vents (if used), Pilot burner flame – Weil-McLain CGa User Manual

Page 9: Main burner flame, Clean vent termination & air intake screens, Check condensate drain system

background image

User’s Information Manual

Part Number 550-110-592/0408

Figure 4
Automatic air
vent

Automatic air vents (if used)

1. See

Figure 4

.

. Remove the cap from any

automatic air vent in the

system and check operation by

depressing valve

B

slightly with

the tip of a screwdriver.

. If the air vent valve appears to be

working freely and not leaking,

replace cap

A

, twisting all the

way on.

. Loosen cap A one turn to allow

vent to operate.

. Have vent replaced if it does not

operate correctly.

Pilot burner flame

Proper

pilot flame (see

Figure 5

):

1. Blue flame.
. Inner cone engulfing thermocouple or thermopile

(standing pilot) or pilot flame sensor (spark-ignited

pilot).

. Thermocouple or thermopile, or pilot flame sensor

glowing cherry red.

Improper

pilot flame:

1. Overfired — Large flame lifting or blowing past pilot

flame sensor.

. Underfired — Small flame. Inner cone not engulfing

pilot flame sensor.

. Lack of primary air — Yellow flame tip.
. Incorrectly heated pilot flame sensor.

Main burner flame

Proper

main burner flame (see

Figure 6

):

1. Yellow-orange streaks may appear (caused by dust).

Improper

main burner flame:

1. Overfired — Large flames.
. Underfired — Small flames.
. Lack of primary air — Yellow tipping on flames

(sooting will occur).

Figure 5 Pilot burner and flame, typical

Figure 6 Main burner flame, typical

Check monthly . . . . . . . . . . . . . . . .

Clean vent termination & air

intake screens

— CGs boilers only

1. Remove all lint and debris from both the boiler air

intake screen and the flue discharge screen.

The boiler control module will sense blockage of

the air intake or flue and lockout if the blockage

is excessive. It will signal the failure by flashing the

appropriate indicator lights on the control board.

. If removing the debris does not allow the boiler to

operate correctly afterwards, contact your qualified

service technician to inspect the boiler and vent/air

systems.

Check condensate drain

system

1. Inspect condensate drain fittings and tubing. Verify

that condensate can flow freely to drain.