beautypg.com

Check daily, Check monthly, Air openings – Weil-McLain CGa User Manual

Page 8: Venting system, Boiler piping, Boiler relief valve

background image

CGa, CGi, CGs, EG, EGH, LGB, PEG, PFG Boilers

Part Number 550-110-592/0408

Check daily . . . . . . . . . . . . . . . . .

Air openings

1. Verify that combustion and ventilation air openings

to the boiler room and/or building are open and
unobstructed.

.

CGs boilers

— Verify that boiler vent discharge

and air intake are clean and free of obstructions.
Remove any debris on the air intake or flue exhaust
openings.

Pressure/temperature gauge

or pressure gauge (steam)

1. Water boilers — Make sure the pressure reading

on the boiler pressure/temperature gauge does
not exceed psig. Higher pressure may indicate a
problem with the expansion tank or gauge.

. Steam boilers — Make sure the pressure reading on

the boiler pressure gauge does not exceed 1 psig.
Higher pressure indicates a problem with the gauge
or limit control.

. Contact a qualified service technician if problem

persists.

Venting system

Failure to inspect the vent system as noted above and

have them repaired by a qualified service technician can

result in vent system failure, causing severe personal

injury or death.

Boiler piping

Have leaks fixed at once by a qualified service technician.

Continual fresh makeup water will reduce boiler life.

Minerals can build up in sections, reducing heat transfer,

overheating cast iron, and causing section failure.

1. Visually inspect for leaks around piping, circulators,

relief valve and other fittings. Immediately call a

qualified service technician to repair any leaks.

1. Visually inspect all parts or the flue gas venting

system for any signs of blockage, leakage or joints

or deterioration of the piping.

.

CGa and EG boilers

:

a. With boiler firing, hold a candle or match below

lower edge of draft hood “skirt.” If flame does

not blow out, but burns undisturbed, the vent

system is working properly.

Do not use

petroleum-based cleaning or sealing

compounds

in boiler system. Severe damage to boiler

and system components can occur, resulting in possible

severe personal injury, death or substantial property

damage.

Check monthly . . . . . . . . . . . . . . . .

If flame blows out or flickers severely, the vent

system must be checked for obstructions or

other causes of improper venting.

b. Verify the vent damper (CGa and EG boilers)

opens before burners ignite.

. Notify your qualified service technician at once if

you find any problem.

Boiler relief valve . . . . . . . . .

1. Inspect the boiler relief valve (see

Figure 3

) and the

relief valve discharge pipe for signs of weeping or

leakage.

. If the relief valve often weeps:

water boilers

— the expansion tank may not

be working properly.

steam boilers

— limit control may be set too

high or there may be system problems.

• Immediately contact your qualified service

technician to inspect the boiler and system.

Figure 3 Relief valve