Operating instructions – Weil-McLain CGa User Manual
Page 18
CGa, CGi, CGs, EG, EGH, LGB, PEG, PFG Boilers
1
Part Number 550-110-592/0408
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
Do not
try
to light the pilot by hand.
B.
BEFORE OPERATING
, smell all around the
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor. See below.
C. Use only your hand to depress or turn the gas control knob. Never
use tools. If the knob will not depress or turn by hand, don’t try to
repair it, call a qualified service technician. Force or attempted repair
may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
1.
STOP!
Read the safety information above on this label.
. Set the thermostat to lowest setting.
. Turn off all electrical power to the appliance.
. Remove front panel.
. This appliance is equipped with an ignition device which
automatically lights the pilot.
Do not
try to light the pilot
by hand.
. Depress gas control knob slightly and turn clockwise
to
“OFF”
.
Note:
Knob cannot be turned to
“OFF”
unless
knob is depressed slightly. Do not force.
1. Set the thermostat to lowest setting.
. Turn off all electric power to the appliance if service is to
be performed.
. Remove front panel.
. Depress gas control knob slightly and turn clockwise
to
“OFF”
. Do not force.
. Replace front panel.
. Wait five () minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
STOP!
Follow
“B”
in the safety information above. If you don’t smell gas,
go to the next step.
. Turn gas control knob counterclockwise
to
“ON”
.
. Turn on all electric power to the appliance.
10. Set thermostat to desired setting.
11. If the appliance will not operate, follow the instructions
To Turn Off Gas To The Appliance
and call your service
technician or gas supplier.
1. Replace front panel.
Operating instructions
• Spark-ignited pilot
•
Gas valve — White-Rodgers 36C
CGa-7, CGa-8,
EG-55 to EG-75,
PEG-55, PFG-5
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
WHAT TO DO IF YOU SMELL GAS
TO TURN OFF GAS TO THE APPLIANCE
550-223-043(0906)