beautypg.com

Installation, Continued) – Wayne CWS50 User Manual

Page 4

background image

4

www.waynepumps.com

Installation

(Continued)

DRIVEN WELL

• Drive the point several feet below

the water table.

NOTE: A packer type foot valve can
be installed in the well (Figure 3,
Illustration B). This type of foot valve
allows the well to be filled with water
when priming and makes the inlet pipe
much easier to test for leaks. Follow
the manufacturer’s instructions when
installing the packer type foot valve.

As an alternative, an in-line check valve
can be used with a driven well (Figure
3, Illustration C). The pipe between the
check valve and the water level will
always be under a vacuum.

Leaking joints or couplings will allow
air to leak into the pipe and cause
abnormal pump operation. Make sure
to use pipe joint compound on all male
pipe threads.

DUG WELL, CISTERN, LAKE AND SPRING
INSTALLATION (FIGURE 17)

• Install a foot valve on inlet pipe and

lower into water.

The foot valve

should be at least 18

in. from the bottom of the well or sand
or sediment could be drawn into the
system.

NOTE: When a lake is used as a water
supply, make sure the inlet pipe is deep
enough to be submerged at all times.
Protect the pipe from damage from
swimmers and boats.

Slope the horizontal piping upward
toward the pump to prevent trapping
air. The pipe must be removed during
winter months or protected against
freezing.

Protect the pipe from damage from
swimmers and boats.

Install a screen

around the inlet

pipe to prevent the entrapment of
swimmers.

DEEP WELL INSTALLATION

DRILLED WELL (4 IN. OR LARGER) WITH
TWO PIPE JET (FIGURES 17 AND 4)

1. Assemble a 1-1/4 in. foot valve (not

included) to the jet body. A 1-1/4 in.
coupling is required to connect the
larger pipe to the jet assembly.

2. Connect the 1 in. pipe threads into

the smaller opening in the jet body.

3. Lower the jet into the well. Add pipe

as needed. Be sure to use pipe joint
compound on all male threads.

4. Position the jet 10 - 20 feet below

the lowest anticipated water level,
but never closer than 5 feet from the
bottom of the well, if possible.

5. Install a well seal to support the pipe

and prevent surface water and other
contaminants from entering the
well.

6. Install the horizontal pipe from

the well to the pump. Piping from
the vertical well pipe to the pump
should never be smaller than the
well pipes.

7. Slope both pipes upward toward

the pump to prevent trapping air. If
the horizontal distance exceeds 25
feet, see Chart 2 (on page 5) for the
recommended pipe sizes.

DUG WELL, CISTERN, LAKE AND SPRING
WITH TWO PIPE JET (FIGURE 17)

1. Install a 1-1/4 in. foot valve (not

included) to the jet body. A 1-1/4 in.
coupling is required to connect the
larger pipe to the jet assembly.

2. Connect the 1 in. pipe threads into

the smaller opening in the jet body.

3. Lower the jet into the water below

the lowest anticipated water level,
but never closer than 18 in. from
the bottom. Sand or debris may be
drawn into the system if the jet is
too close to the bottom.

4. Provide protection for the jet and

pipes against damage from boats
or swimmers if a lake is used for the
water supply.

Install a screen

around the inlet

pipe to prevent the entrapment of
swimmers.

5. Slope the horizontal pipes upward

toward the pump to prevent
trapping air. If horizontal distance
exceeds 25 feet, see Chart 2 for
recommended pipe sizes.

DRILLED WELL (2 IN.) WITH SINGLE PIPE
PACKER (FIGURES 17 AND 5)

NOTE: Single pipe packer jets rely on
the space between single pipe and
inside of well casing for return water to
operate jet. Two inch installations must
use 1-1/4 in. galvanized steel pipe with
special turned couplings (1-13/16 in.
O.D.) to avoid restricting flow of return
water back to jet.

1. Assemble the foot valve and packer

to the jet body.

2. Lubricate the rubber cups with

petroleum jelly.

3. Attach the first section of pipe and

lower jet into well.

4. Add pipe until the jet is positioned 5 -

15 feet below the lowest anticipated
water level. The jet should never be
closer than 5 feet from the bottom of
the well or sand and sediment may
be drawn into the system.

5. With the jet in position, fill the pipes

with water to make sure the rubber
cups are sealed against inside of the
well casing. It may be necessary to
move the jet up and down to seat
the cups.

6. Install the casing adapter and the

horizontal pipes.

Operating Instructions & Parts Manual

CWS50, CWS75 and CWS100

Figure 4 - Two Pipe Jet

Jet Body

Foot Valve

1-1/4 in. Pipe

1 in.
Pipe

Figure 5 - Single Pipe Jet

Packer

Foot Valve

1-1/4 in. Pipe

Cups

CHART 2 - PIPE SIZING

Pump Model

Pump
Opening

Horizontal Distance

(Feet)

0-25

26-100

Deep Well

Inlet:
Suction

1-1/4 in.

1-1/2 in.

Inlet: Drive

1 in.

1-1/4 in.

Outlet

3/4 in.

1 in.

This manual is related to the following products: