Air movement recordings – Unified Brands VENTILATION SYSTEMS User Manual
Page 30

27
AIR MOVEMENT RECORDINGS
(Supplement to Ventilator Installation/Start Up Report)
Project Name
Readings Taken by:
A. ENERGY AIRE HOODS - EXHAUST
1. Reading No. 1, 2, and 3 are taken at the front
middle, and back of the intake slot.
2. For 8 foot hood sections and less, take three
[3] readings at each of three [3] locations:
1 foot from each end, and one [1] reading in
the middle.
3. For hood sections over 8 feet in length, take
three [3] readings at each of four [4] locations:
1 foot from each end, and two [2] readings in
the middle.
4. B. FILTER HOODS - EXHAUST
1. Take Reading No. 1, 2, and 3 on vertical
centerlines.
2. Refer to A.2, 3.
C. SUPPLY PLENUM
1. Reading No. 1 only is used.
2. Take readings on horizontal centerline of grill.
3. Refer to A.2, 3, but only one reading at each
location
AVTEC INDUSTRIES INC. 1055 MENDELL DAVIS DR. JACKSON, MS 39272 [888] 994-7636
form no. 14018 1998 AVTEC Industries inc.