Terminal block designation – Unified Brands VENTILATION SYSTEMS User Manual
Page 11

8
Terminal Block Designation
[For authorized sevice techinician use only]
B. PAWS Control Panel
TB-1
1-Line Hot
2-Line Neutral
Incoming Power Supply 120vac, 15 amps, 60 Hz
3-Mech. Ground
TB-2
1-Switched Hot
2-Neutral
Wash Solenoid #1, 120vac, 1.5 amps max
3-Switched Hot
4-Neutral
Wash Solenoid #2, 120vac, 1.5amps max
5-Switched Hot
6-Neutral
Wash Solenoid #3, 120vac, 1.5amps max
TB-3
1-Switched Hot
2-Neutral
Wash Solenoid #4 120vac, 1.5amps max
3-Switched Hot
4-Neutral
Wash Solenoid #5 120vac, 1.5amps max
5-Switched Hot
6-Neutral
Wash Solenoid #6 120vac, 1.5amps max
TB-4
1-Switched Hot
2-Neutral
Wash Solenoid #7 120vac, 1.5amps max
3-Switched Hot
4-Neutral
Wash Solenoid #8 120vac, 1.5amps max
TB-5
1-Switched Hot
2-Neutral
Detergent Pump, 120vac, 1.5apms max
3-Switched Hot
4-Neutral
PAWS Alarm Horn, 120vac, 1.5amps max
5-Switched Hot
6-Neutral
Fan Contractor, 120vac, 1.5amps max
TB-6
1-Switched Hot
2-Neutral
Spare Output [PAW] 120vac 1.5amps max
*3-Switched Hot
*4-Neutral
Spare Output [MAF II] 120vac, 1.5amps max
5-Neutral
Auxillary
6-Hot
Power Tap
120vac, 120amps max
TB-7
*1-NC
*2-C
Trouble Dry Contacts [MAF II] 1.5amps @ 28vdc/120vac
*3-NO
*4-NC
*5-C
Trouble Dry Contacts [MAF II] 1.5amps @ 28vdc/120vac
*6-NO
TB-8
*1-NC
*2-C
Fire Dry Contacts [MAF II] 1.5amps @ 28vdc/120vac
*3-NO
*4-NC
*5-C
Fire Dry Contacts [MAF II] 1.5amps @ 28vdc/120vac
*6-NO
TB-9
1-Line Hot
PAWS Supervised
]
2-Switched Hot
Valve Switch
|
3-Line Hot
PAWS Manual
|
120vac, 25 milliamps
4-Switched Hot
Fire Pull Switch
|
5-Line Hot
PAWS Automatic |
6-Switched Hot
Fire Switch
]
TB-10
*1-Line Hot
MAF II Water
]
*2-Switched Hot
Flow Switch
|
*3-Line Hot
MAF II Water
|
12vdc, 25 milliamps
*4-Switched Hot
Pressure Switch
|
*5-Line Hot
MAF II Supervised |
*6-Switched Hot
Valve Switch
]
TB-11
1-Detergent
2-Probe
20vdc, 2 milliamps
*3-Positve
*4-Negative
MAF II Horn, 12vdc, 1.5amps
TB-12
1-Positve
2-Negative
Battery, 12v, 5A Hours
3-Positve
Auxillary
4-Negative
Power Tap
*See “Mist-A-Fire Technical Manual” (fig. 10)